![ABB ACS355 series User Manual Download Page 387](http://html.mh-extra.com/html/abb/acs355-series/acs355-series_user-manual_2968387.webp)
Technical data 387
Control connection data
Analog inputs
X1A: 2 and 5
(AI1 and AI2)
Voltage signal,
unipolar
0 (2)…10 V,
R
in
= 675 kohm
bipolar
-10…10 V,
R
in
= 675 kohm
Current signal,
unipolar
0 (4)…20 mA,
R
in
= 100 ohm
bipolar
-20…20 mA,
R
in
= 100 ohm
Potentiometer reference
value (X1A: 4)
10 V ± 1%, max. 10 mA,
R
< 10 kohm
Resolution
0.1%
Accuracy
±2%
Analog output
X1A: 7
(AO)
0 (4)…20 mA, load < 500 ohm
Auxiliary voltage
X1A: 9
24 V DC ± 10%, max. 200 mA
Digital inputs
X1A: 12…16
(DI1…DI5)
Voltage
12…24 V DC with internal or external
supply. Max. voltage for digital inputs
30 V DC.
Type
PNP and NPN
Input impedance,
X1A: 12…15
R
in
= 2 kohm
X1A: 16
R
in
= 4 kohm
Frequency input
X1A: 16
(DI5)
X1A: 16 can be used either as a digital or as a frequency input.
Frequency
Pulse train 0…10 kHz with 50% duty
cycle. 0…16 kHz between two
ACS355 drives.
Relay output
X1B: 17…19
(RO 1)
Type
NO + NC
Max. switching voltage
250 V AC / 30 V DC
Max. switching current
0.5 A / 30 V DC; 5 A / 230 V AC
Max. continuous current
2 A rms
Digital output
X1B: 20…21
(DO)
Type
Transistor output PNP
Max. switching voltage
30 V DC
Max. switching current
100 mA / 30 V DC, short-circuit
protected
Frequency
10 Hz …16 kHz
Resolution
1 Hz
Accuracy
0.2%
Frequency output
X1B: 20…21
(FO)
X1A: 20…21 can be used either as a digital or as a frequency output.
STO interface
X1C: 23…26
Appendix: Safe torque off (STO)
Clearance and creepage distance
Clearance and creepage distance between I/O connections and the main circuit is
5.5 mm (0.20 in). This meets the requirement for the reinforced insulation of
overvoltage category 3 when the installation altitude is below 2000 m (6562 ft). (EC
61800-5-1).
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...