204 Actual signals and parameters
1302 MAXIMUM AI1 Defines the maximum %-value that corresponds to
maximum mA/(V) signal for analog input AI1. When used as
a reference, the value corresponds to the reference
maximum setting.
0…20 mA 0…100%
4…20 mA 20…100%
-10…10 mA -50…50%
Example:
If AI1 is selected as the source for external
reference REF1, this value corresponds to the value of
parameter
100.0%
-100.0…100.0% Value as a percentage of the full signal range.
Example:
If the maximum value for analog input is 10 mA,
the percentage value for 0…20 mA range is:
(10 mA / 20 mA) · 100% = 50%
1 = 0.1%
1303 FILTER AI1
Defines the filter time constant for analog input AI1, ie, the
time within which 63% of a step change is reached.
0.1 s
0.0…10.0 s
Filter time constant
1 = 0.1 s
1304 MINIMUM AI2
Defines the minimum %-value that corresponds to minimum
mA/(V) signal for analog input AI2. See parameter
.
20%
.
1 = 0.1%
1305 MAXIMUM AI2 Defines the maximum %-value that corresponds to
maximum mA/(V) signal for analog input AI2. See
parameter
100.0%
.
1 = 0.1%
1306 FILTER AI2
Defines the filter time constant for analog input AI2. See
parameter
0.1 s
0.0…10.0 s
Filter time constant
1 = 0.1 s
All parameters
No.
Name/Value
Description
Def/FbEq
=
=
=
Unfiltered signal
Filtered signal
Time constant
63
100
%
t
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...