Fault tracing 359
Missing input power line
phase.
Measure the input and DC voltage
during start, stop and running by using
a multimeter or check parameter
Blown fuse
Check the condition of input fuses.
Rectifier bridge internal
fault.
Replace the drive.
0007
AI1 LOSS
(8110)
bit 6
(programmable
fault function
,
Analog input AI1 signal
has fallen below limit
defined by parameter
.
Analog input signal is
weak or does not exist.
Check the source and wire
connections of the analog input.
Analog input signal is
lower than fault limit.
and
0008
AI2 LOSS
(8110)
bit 7
(programmable
fault function
,
Analog input AI2 signal
has fallen below limit
defined by parameter
.
.
Analog input signal is
weak or does not exist.
Check the source and wire
connections of analog input.
Analog input signal is
lower than fault limit.
and
CODE FAULT
CAUSE
WHAT TO DO