256 Actual signals and parameters
3022 AI2 FAULT
LIMIT
Defines a fault level for analog input AI2. If parameter
, the drive trips on fault
) when the analog input signal falls below
the set level.
Do not set this limit below the level defined by parameter
.
0.0%
0.0…100.0%
Value as a percentage of the full signal range
1 = 0.1%
3023 WIRING FAULT Selects how the drive reacts when incorrect input power and
motor cable connection is detected (ie, the input power
cable is connected to the motor connection of the drive).
Note:
Disabling wiring fault (ground fault) may void the
warranty.
DISABLE
No action
0
ENABLE
The drive trips on fault
).
1
3025 STO
OPERATION
Selects how the drive reacts when the drive detects that the
STO (Safe torque off) function is active.
ONLY FAULT
The drive trips on fault
1
ALARM&FAUL
T
The drive generates alarm
)
when stopped and trips on fault
(
) when running.
2
NO & FAULT
The drive gives no indication to the user when stopped and
trips on fault
(
) when running.
3
ONLY ALARM
The drive generates alarm
).
Note:
The start signal must be reset (toggled to 0) if STO
(Safe torque off) has been used while the drive has been
running.
4
3026 POWER FAIL
START
Selects how the drive reacts when the control board is
externally powered by the MPOW-01 auxiliary power
extension module (see
on
) and start is requested by the user.
ALARM
The drive generates alarm
(
).
1
FAULT
The drive trips on fault
).
2
NO
The drive gives no indication to the user.
3
3027 OPTION COM
LOSS
Selects how the drive reacts when the MREL-01 output
relay module is removed from the drive, and parameters
have non-zero values.
1
DISABLE
No action.
0
ENABLE
The drive trips on fault
.
1
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...