SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.79-O3
ISSUE DATE: 11/09/2018
2
This screen is the top level of the general configura-
tion parameters. It allows programming of the time and
date, along with specifications as to how the time will
be displayed (12 or 24 hour format). In addition, the
chiller configuration, as determined by the state of the
Microboard Program Jumpers and Program Switches
is displayed. A qualified Service Technician, following
instructions in Service Manual (Form 160.69-M1-C),
establishes this configuration per the desired opera-
tion. This screen also serves as a gateway to more sub-
screens for defining general system parameters.
PROGRAMMABLE
Refrigerant Selection
Access Level Required: SERVICE
Displays
R134a
or
R22
as set by position of SW1-1
On = R134a.
Liquid Type
Displays
Water
or
Brine
as set by position of SW1-2
Off = Water.
Chilled Liquid Pump Operation:
Access Level Required: SERVICE
Displays as
Standard
or
Enhanced
.
Anti-Recycle:
Access Level Required: SERVICE
Selectable as
Disabled
or
Enabled
.
Power Failure Restart:
Access Level Required: SERVICE
Selectable as
Manual
or
Automatic
.
Motor Drive Type
Access Level Required: SERVICE
Sets the type of Starter that is installed. EM, VSD - 60
Hz, VSD - 50 Hz, or MVVSD.
Coastdown Time
Access Level Required: SERVICE
Sets the Coastdown Time:
Standard
(150 seconds) or
Enhanced
(15 minutes – Steam Turbine applications)
Pre-Run
Access Level Required: OPERATOR
Sets the duration of the system pre-lube:
Standard
(50 seconds) or
Extended
(180 seconds)
Line Frequency
Access Level Required: SERVICE
Sets the Line Frequency: 50 Hz or 60 Hz.
SETUP SCREEN
LD27874
FIGURE 35 -
SETUP SCREEN