JOHNSON CONTROLS
100
FORM 160.79-O3
ISSUE DATE: 11/09/2018
SECTION 2 – OPTIVIEW CONTROL CENTER
Motor Heaters
Access Level Required: SERVICE
Is set to Enabled if optional Motor Heaters are installed
or Disabled if they are not installed.
Safety Stop
Access Level Required: SERVICE
Displays Enabled, indicating that the Safety Stop
switch is installed on the control panel.
Present Date
Access Level Required: OPERATOR
Allows the user to specify the present date. This value
is critical to logging system shutdowns accurately and
for utilizing the scheduling capabilities. When prompt-
ed to enter a date value, the user must enter the day,
month, and four-digit year (using leading zeroes as
necessary). If within range, the value will be accepted.
If out of range, the user is prompted for the informa-
tion again. At this point the user may retry the date
entry, or cancel the programming attempt.
Present Time
Access Level Required: OPERATOR
Allows the user to specify the present time. This value
is critical to logging system shutdowns accurately and
for utilizing the scheduling capabilities. When prompt-
ed to enter a time value, the user must enter the hour
and minute desired (using leading zeroes as necessary).
If the chiller is presently set to 24-hour mode, the time
must be entered in the 24-hour format. Otherwise, the
user must also select AM or PM for the entered time. If
out of range, the user is prompted for the information
again. At this point, the user may retry the time entry
or cancel the programming attempt.
12/24 Hr
Access Level Required: OPERATOR
Allows the user to specify the format in which the
time will be presented to the user. This setpoint will
affect the display of the time on the chiller panel and
on all reports generated. 12-Hour time format will in-
clude the AM and PM modifiers and show the range of
time between 1:00 and 12:59, while the 24-Hour time
format will show the range of time between 0:00 and
23:59.
Change Settings
Access level Required: OPERATOR or higher
Used to enter the following setpoints. Pressing this key
places a green selection box around the first change-
able setpoint. The access level determines which set-
points can be changed. Use the ▲ and ▼ keys to place
the selection box around the desired setpoint. With the
setpoint selected, press the ENTER (√) key. A dialog
box appears with the range of settings.
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home screen.
Schedule
Access Level Required: VIEW
Moves to the subscreen allowing definition of the
chiller operation schedule.
User
Access Level Required: VIEW
Moves to the subscreen allowing configuration of user
preferences.
Comms
Access Level Required: VIEW
Moves to the subscreen allowing configuration of sys-
tem communications.
Printer
Access Level Required: VIEW
Moves to the subscreen allowing configuration and
control of printer functions.
Sales Order
Access Level Required: VIEW
Moves to the subscreen displaying the Sales Order in-
formation for the chiller system.
Operations
Access Level Required: VIEW
Moves to the subscreen displaying operating param-
eters of the chiller system.
Diagnostics
Access Level Required: SERVICE
Moves to the subscreen, displaying operating param-
eters of the chiller system.