This screen allows calibration of the compressor
Variable Geometry Diffuser position potentiometer.
Requires a login access level of
SERVICE.
DISPLAY ONLY
VGD Opening (LED)
Illuminates when an open signal is being applied to the
VGD.
VGD Closing (LED)
Illuminates when a close signal is being applied to the
VGD.
VGD Feedback Voltage
Displays the VGD position potentiometer feedback
voltage.
Calibration In Progress (LED)
Illuminates when a calibration sequence is in progress.
Calibration Messages
These are text messages which step the user through
the calibration process and indicate its success or
failure.
PROGRAMMABLE
Start Calibration
Initiates the calibration start.
Cancel Calibration
This button is displayed during the VGD calibration
process. It allows the user to cancels a calibration se-
quence that is in progress.
NAVIGATION
Home
Access Level Required: SERVICE
Causes an instant return to the Home Screen.
VGD 1 or 2
Access Level Required: SERVICE
Moves to the VGD 1 subscreen that allows viewing of
the associated VGD parameters.
VARIABLE GEOMETRY DIFFUSER (VGD) CALIBRATION SCREEN
FIGURE 15 -
VARIABLE GEOMETRY DIFFUSER 1 CALIBRATION SCREEN
LD27854