JOHNSON CONTROLS
153
SECTION 3 – PRINTERS
FORM 160.79-O3
ISSUE DATE: 11/09/2018
3
[Skip the following section if Motor Type is not EM]
Electro-Mechanical Starter
----------------------------------------------------------------------------------
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %
Remote Digital Current Limit
= 100 %
Remote Modem Current Limit
= 100 %
Pulldown Demand Limit
= 100 %
Pulldown Demand Time
= 0 Min
[Skip the following section if Motor Type is not Mod A
SSS]
Liquid-Cooled Solid State Starter
----------------------------------------------------------------------------------
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %
Remote Digital Current Limit
= 100 %
Remote Modem Current Limit
= 100 %
Pulldown Demand Limit
= 100 %
Pulldown Demand Time
= 0 Min
Scale/Model
= 600 V, 281 A
Supply Voltage Range
= Disabled
Full Load Amps
= 150 A
Current Imbalance Check
= Disabled
[Skip the following section if Motor Type is not Mod B
SSS]
Liquid-Cooled Solid State Starter
----------------------------------------------------------------------------------
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %
Remote Digital Current Limit
= 100 %
Remote Modem Current Limit
= 100 %
Pulldown Demand Limit
= 100 %
Pulldown Demand Time
= 0 Min
Starter Model
= 26L
Voltage Range
= 440 - 480
Full Load Amps
= 275 A
Starting Current
= 1150 A
Open SCR
= Enabled
FIGURE 55 -
SAMPLE PRINTOUT (SETPOINTS) (CONT'D)
Shorted SCR
= Disabled
[Skip the following section if Motor Type is not VSD]
Variable Speed Drive
----------------------------------------------------------------------------------
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %
Remote Digital Current Limit
= 100 %
Remote Modem Current Limit
= 100 %
Pulldown Demand Limit
= 100 %
Pulldown Demand Time
= 0 Min
Motor HP
= 351 HP
Power Line Frequency
= 60Hz
[Skip the following section if Motor Type is not VSD]
Harmonic Filter Data
----------------------------------------------------------------------------------
Filter Operation
= Enabled
Motor HP
= 351 HP
[Skip the following section if Motor Type is not VSD]
Adaptive Capacity Control
----------------------------------------------------------------------------------
Surge Margin Adjust
= 0 Hz
Stability Limit
= 4500
FIGURE 55 -
SAMPLE PRINTOUT (SETPOINTS) (CONT'D)