SECTION 2 – OPTIVIEW CONTROL CENTER
Remote Analog Input Range
Access Level Required: OPERATOR
Defines the remote signal range applied for remote re-
set of the Leaving Chilled Liquid temperature Setpoint
and Current Limit Setpoint in ANALOG remote mode.
If the remote signal is 0-10 VDC or 0-20 mA, this set-
point must be programmed for 0-10 VDC. If the remote
signal is 2-10 VDC or 4-20 mA, this setpoint must be
programmed for 2-10 VDC.
Access Level Required: VIEW
Prints the Setpoints report.
NAVIGATION
Home
Access Level Required: VIEW
Causes an instant return to the Home screen.
Setup
Access Level Required: VIEW
Moves to the subscreen allowing setup of general sys-
tem parameters.