SECTION 2 – OPTIVIEW CONTROL CENTER
Evaporator Pressure
Displays the present refrigerant pressure in the evapo-
rator.
Evaporator Saturation Temperature
Displays the present saturation temperature in the
evaporator.
Condenser Liquid Temperature - Leaving
Displays the temperature of the liquid as it leaves the
condenser.
Condenser Liquid Temperature - Entering
Displays the temperature of the liquid as it enters the
condenser.
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Condenser Saturation Temperature
Displays the saturation temperature in the condenser.
Oil Sump Temperature
Displays the temperature of the oil in the sump.
Chiller Current Limit Setpoint
Displays the Chiller Current Limit Setpoint. The Chill-
er Current Limit Setpoint could be from a 0-20 mA,
4-20 mA, 0-10 VDC or 2-10 VDC input in Analog re-
mote mode or PWM input in Digital remote mode or
SC-EQ communication interface in ISN (BAS) remote
mode or a Local Chiller Limit Setpoint entered at the
Keypad.
This setpoint is in effect after the Lead Compressor
Pulldown Time setpoint has elapsed and for the re-
mainder of system run.
PROGRAMMABLE
None
NAVIGATION
Home
Access Level Required:
VIEW
Causes an instant return to the Home Screen.