JOHNSON CONTROLS
67
SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.79-O3
ISSUE DATE: 11/09/2018
2
Manual Increment
Sets the percentage amount that the PRV or HGBP will
move with each press of the Manual Increase or De-
crease button. (Adjustable between 0.1% and 10%)
Increase
Opens the selected PRV or HGBP with each press by
the amount set in the Manual Increment setting.
Decrease
Closes the selected PRV or HGBP with each press by
the amount set in the Manual Increment setting.
Set
Allows the service technician to set the selected PRV
or HGBP to a desired position between 05 and 100%
for testing.
Auto
Returns the manually controlled PRV or HGBP back to
Automatic program control.
NAVIGATION
Home
Causes an instant return to the Home screen.
Capacity Cycling
Causes an instant jump to the Capacity Cycling screen
where the Operator can set the Compressor staging and
lockout a compressor.
Compressor
Causes an instant navigation to the Compressor screen.
Setpoints
Navigates to the Capacity Control Setpoints screen.
Hot Gas
Causes an instant navigation to the Hot Gas screen if
that option is installed.