JOHNSON CONTROLS
54
FORM 160.79-O3
ISSUE DATE: 11/09/2018
SECTION 2 – OPTIVIEW CONTROL CENTER
The minimum difference between the High Limit
setpoint and the Low Limit setpoint is 0.1 VDC. If a
Low Limit setpoint is entered which is less than 0.1
VDC below the High Limit setpoint, the High Limit
setpoint is adjusted so that it is 0.1 VDC above the
newly entered Low Limit value.
NAVIGATION
Home
Access Level Required: Service
Causes an instant return to the Home Screen
VGD 1
Access Level Required: Service
Causes an instant return to the Variable Geometry Dif-
fuser 1 Screen
VGD 2
Access Level Required: Service
Causes an instant return to the Variable Geometry Dif-
fuser 2 Screen