JOHNSON CONTROLS
29
SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.79-O3
ISSUE DATE: 11/09/2018
2
ANALOG INPUT RANGES
The following table indicates the valid display range
for each of the analog input values. In the event that the
input sensor is reading a value outside of these ranges,
the < or > symbols will be displayed beside the mini-
mum or maximum value, respectively.
ANALOG INPUT
ENGLISH RANGE
METRIC RANGE
LOW
HIGH
UNITS
LOW
HIGH
UNITS
Leaving Chilled Liquid Temperature
0.0
82.0
°
F
-17.7
27.7
°
C
Return Chilled Liquid Temperature
0.0
94.1
°
F
-17.7
34.5
°
C
Leaving Condenser Liquid Temperature
8.0
133.5
°
F
-13.3
56.3
°
C
Return Condenser Liquid Temperature
8.0
133.5
°
F
-13.3
56.3
°
C
Evaporator Refrigerant Temperature (Optional)
0.0
126.1
°
F
-17.7
52.3
°
C
Discharge Temperature
31.8
226.3
°
F
-0.1
107.9
°
C
Oil Temperature
31.8
226.3
°
F
-0.1
107.9
°
C
Condenser Pressure
0.0
315.0
PSIG
0.0
2172.4
KPAG
Condenser Temperature*
-98.7
160.1
°
F
-72.6
71.7
°
C
Evaporator Pressure
5.5
77.4
PSIG
37.9
533.7
KPAG
Evaporator Temperature*
-44.9
64.7
°
F
-42.7
18.1
°
C
Oil Sump Pressure
0.0
315.0
PSIG
0.0
2172.4
KPAG
High Speed Thrust Bearing Proximity Position
8.0
99.0
MILS
8.0
99.0
MILS
Refrigerant Level
0.0
100.0
%
0.0
100.0
%
Drop Leg Refrigerant
0.0
121.7
°
F
-17.7
49.8
°
C
*Saturation temperatures are calculated values. They will display XXX if the pressure used for the calculation is out of range.