SECTION 2 – OPTIVIEW CONTROL CENTER
Motor Cooling Coil Leak Detected (LED)
Illuminates when the enabled Motor Cooling Coil
Leak Detector indicates a leak. The LED and text de-
scription do not appear when the Motor Cooling Coil
Leak Protection option is not installed.
Motor Bearings
Temperature
Displays the enabled Shaft End and Opposite End mo-
tor bearing temperatures. Any RTD input that registers
as an open RTD, is considered invalid and displays as
XXX.X. When the Bearing Temperature Protection
option is not installed, no temperatures are displayed
and the heading, text and data boxes do not appear.
Vibration
Displays the Shaft End and Opposite End vibration
values. The vibration values are not in any particular
units of measure. They are relative values. The larger
the number, the greater the magnitude of vibration rep-
resented. When the Motor Vibration Protection option
is not installed, no vibration values are displayed and
the heading, text and data boxes do not appear.
Vibration Baseline
Displays the Shaft End and Opposite End vibration val-
ues established during the initial startup of the chiller.
PROGRAMMABLE
None.
NAVIGATION
Home
Access Level Required: VIEW
Returns the user to the Home screen.
Motor
Access Level Required: VIEW
Returns the user to the Motor screen.