SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.79-O3
ISSUE DATE: 11/09/2018
2
Lead Compressor Pulldown Demand Limit
Access Level Required: OPERATOR
Sets the maximum current draw of the lead compres-
sor during initial start for the selected Pulldown Time.
(Adjustable between 30 and 100%, Default = 100%)
Lead Compressor Pulldown Time
Access Level Required: OPERATOR
Sets the amount of time that the lead compressor pull-
down demand limit setpoint will be in effect. (Adjust-
able between 0 and 255 minutes, Default = 0 minutes).
NAVIGATION
Home
Access Level Required: VIEW
Returns user to the Home screen.
VSD 1
Access Level Required: VIEW
Moves to the subscreen which provides more informa-
tion about Variable Speed Drive 1.
VSD 2
Access Level Required: VIEW
Moves to the subscreen which provides more informa-
tion about Variable Speed Drive 2.