386
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Table 5.7 Multi-function Input Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Digital Inputs
S1
MFDI selection 1
(ON: Forward run OFF: Stop)
•
Photocoupler
•
24 V, 6 mA
Note:
Install the wire jumpers between terminals SC-SP and SC-SN to set the MFDI power supply
(sinking/sourcing mode or internal/external power supply).
•
Sinking Mode: Install a jumper between terminals SC and SP.
NOTICE:
Damage to Equipment. Do not close the circuit between
terminals SC-SN. If you close the circuits between terminals SC-SP
and terminals SC-SN at the same time, it will cause damage to the
drive.
•
Sourcing Mode: Install a jumper between terminals SC and SN.
NOTICE:
Damage to Equipment. Do not close the circuit between
terminals SC-SP. If you close the circuits between terminals SC-SP
and terminals SC-SN at the same time, it will cause damage to the
drive.
•
External power supply: No jumper necessary between terminals SC-SN and terminals SC-SP.
S2
MFDI selection 2
(ON: Reverse run OFF: Stop)
S3
MFDI selection 3
(External fault (N.O.))
S4
MFDI selection 4
(Fault reset)
S5
MFDI selection 5
(Multi-step speed reference 1)
S6
MFDI selection 6
(Multi-step speed reference 2)
S7
MFDI selection 7
(Jog command)
S8
MFDI selection 8
(Baseblock command (N.O.))
SN
MFDI power supply 0 V
MFDI power supply, 24 V (maximum 150 mA)
NOTICE:
Damage to Equipment. Do not close the circuit between
terminals SP-SN. If you close the circuits between terminals SC-SP and
terminals SC-SN at the same time, it will cause damage to the drive.
SC
MFDI selection common
SP
MFDI power 24 Vdc
Safe Disable
Input
H1
Safe Disable input 1
Remove the jumper between terminals H1-HC and H2-HC to use the Safe Disable input.
•
24 V, 6 mA
•
ON: Normal operation
•
OFF: Coasting motor
•
Internal impedance 4.7 kΩ
•
OFF Minimum OFF time of 2 ms.
H2
Safe Disable input 2
HC
Safe Disable function common
Safe Disable function common
NOTICE:
Do not close the circuit between terminals HC and SN. A
closed circuit between these terminals will cause damage to the drive.
Master
Frequency
Reference
RP
Master frequency reference pulse train input
(Master frequency reference)
•
Response frequency: 0 Hz to 32 kHz
•
H level duty: 30% to 70%
•
H level voltage: 3.5 V to 13.2 V
•
L level voltage: 0.0 V to 0.8 V
•
Input impedance: 3 kΩ
+V
Power supply for frequency setting
10.5 V (allowable current 20 mA maximum)
-V
Power supply for frequency setting
-10.5 V (allowable current 20 mA maximum)
A1
MFAI1
(Master frequency reference)
Voltage input or current input
Select terminal A1 with DIP switch S1-1 and
H3-01 [Terminal A1 Signal Level Select]
.
Select terminal A2 with DIP switch S1-2 and
H3-09 [Terminal A2 Signal Level Select]
•
-10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
•
0 V to 10 V/100% (input impedance: 20 kΩ)
•
4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
A2
MFAI2
(Combined to terminal A1)
A3
MFAI3/PTC input
(Auxiliary frequency reference)
•
Voltage input or current input
Select using DIP switch S1-3 and
H3-05 [Terminal A3 Signal Level Select]
.
–
-10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
–
0 V to 10 V/100% (input impedance: 20 kΩ)
–
4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
•
PTC input (Motor Overheat Protection)
Set DIP switch S4 to
“
PTC
”
and set DIP switch S1-3 to
“
V
”
to set terminal A3 for PTC input.
AC
Frequency reference common
0 V
E (G)
Connecting shielded cable
-
■
Output Terminals
Refer to
and
for a list of Output terminals and functions.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...