3.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
276
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
No.
Name
Range
Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
EZOLV
(8)
E1-08
Mid Point A Voltage
0.0 - 255.0
0.1 V
-
-
-
-
E1-09
Minimum Output
Frequency
0.0 - 590.0
0.1 Hz
Determined by E5-01 Determined by E5-01 Determined by E5-01
-
E1-10
Minimum Output
Voltage
0.0 - 255.0
0.1 V
-
-
-
-
E1-11
Mid Point B Frequency
0.0 - 590.0
0.1 Hz
-
-
-
-
E1-12
Mid Point A Voltage
0.0 - 255.0
0.1 V
-
-
-
-
E1-13
Base Voltage
0.0 - 255.0
0.1 V
-
-
-
-
F1-01
Encoder 1 Pulse Count
(PPR)
0 - 60000
1 ppr
-
-
1024
-
F1-05
Encoder 1 Rotation
Selection
0 - 1
1
-
-
1
-
F1-09
Overspeed Detection
Delay Time
0.0 - 2.0
0.1 s
-
0.0
0.0
0.0
L1-01
Motor Overload (oL1)
Protection
0 - 6
1
4
4
5
1
L2-31
KEB Start Voltage
Offset Level
0 - 100
1 V
50
50
50
50
L3-05
Stall Prevention during
RUN
0 - 3
1
2
-
-
3
L3-20
DC Bus Voltage
Adjustment Gain
0.00 - 5.00
0.01
0.65
0.65
0.65
0.65
L3-21
OVSuppression Accel/
Decel P Gain
0.10 - 10.00
0.01
1.00
1.00
1.00
1.00
L3-36
Current Suppression
Gain@Accel
0.0 - 100.0
0.1
-
-
-
-
L4-01
Speed Agree Detection
Level
0.0 - 590.0
0.1
0.0 Hz
0.0%
0.0%
0.0 Hz
L4-02
Speed Agree Detection
Width
0.0 - 20.0
0.1
2.0 Hz
4.0%
4.0%
2.0 Hz
L4-03
Speed Agree Detection
Level(+/-)
-590.0 - +590.0
0.1
0.0 Hz
0.0%
0.0%
0.0 Hz
L4-04
Speed Agree Detection
Width(+/-)
0.0 - 20.0
0.1
2.0 Hz
4.0%
4.0%
2.0 Hz
L8-38
Carrier Frequency
Reduction
0 - 2
1
0
-
0
0
L8-40
Carrier Freq Reduction
Off-Delay
0.00 - 2.00
0.01 s
0.00
-
0.00
0.00
L8-90
STPo Detection Level
(Low Speed)
0 - 5000
1
0
80
-
0
n1-15
PWM Voltage Offset
Calibration
0 - 2
1
1
1
1
1
n5-04
Speed Response
Frequency
0.00 - 500.00
0.01 Hz
-
20.00
50.00
-
n8-35
Initial Pole Detection
Method
0 - 2
1
0
1
1
-
n8-51
Pull-in Current @
Acceleration
0 - 200
1%
50%
-
-
80%
o1-03
Frequency Display Unit
Selection
0 - 3
1
2
2
2
0
o1-04
V/f Pattern Display Unit 0 - 1
1
-
1
1
0
*1
The default setting is different for different models.
•
2138 - 2415, 4089 - 4720, T103 - T720: 0.30
*2
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
*3
The setting range is 0.0 to 100.0 when
A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector]
.
*4
The setting range is 0.0 to 40.0 when
A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector]
.
*5
The default setting changes when
C6-01 [Normal / Heavy Duty Selection]
changes.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...