5.6
Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
•
MFDI (terminals S1 to S8)
•
Pulse train output (terminal MP)
•
MFAI (terminals A1 to A3)
•
PTC input (terminal A3)
•
MFAO (terminals FM, AM)
•
MEMOBUS/Modbus communications (terminals D+, D-, AC)
◆
Set Sinking Mode/Sourcing Mode
Close the circuit between terminals SC-SP and SC-SN to set the sinking mode/sourcing mode and the internal/
external power supply for the MFDI terminals. The default setting for the drive is internal power supply sinking
mode.
NOTICE:
Damage to Equipment. Do not close the circuit between terminals SP-SN. If you close the circuits between terminals SC-
SP and terminals SC-SN at the same time, it will cause damage to the drive.
Mode
Internal Power Supply (Terminal SN-SP)
External 24 V power supply
Sinking Mode (NPN)
Sourcing Mode
(PNP)
◆
Pulse Train Output
You can use pulse train monitor output terminal MP for sourcing mode or for sinking mode.
•
Use for sourcing mode
The load impedance changes the voltage level of the pulse train output signal.
Load Impedance
R
L
(k
Ω
)
Output Voltage
V
MP
(V)
1.5 kΩ or more
5 V or more
4.0 kΩ or more
8 V or more
10 kΩ or more
10 V or more
Note:
Use the formula in
to calculate the necessary load resistance (kΩ) to increase output voltage V
MP
(V).
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...