110
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Code
Name
Causes
Possible Solutions
rF
Braking Resistor Fault
The resistance of the dynamic braking option that is
connected to the drive is too low.
Use a dynamic braking option that fits the model and duty rating of
the drive.
A regenerative converter, regenerative unit, or
braking unit is connected to the drive.
Set
L8-55 = 0 [Internal DB TransistorProtection = Disable]
.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
rH
Braking Resistor Overheat
The deceleration time is too short and excessive
regenerative energy is flowing back into the drive.
•
Check the load level, deceleration time, and speed.
•
Decrease the load.
•
Increase the values set in
C1-02, C1-04, C1-06, or C1-08
[Deceleration Times]
.
•
Use a dynamic braking option that lets you use more power.
The duty cycle is too high.
Examine the duty cycle.
Note:
When
L8-01 = 1 [3% ERF DB Resistor Protection = Enabled]
,
the maximum braking duty cycle is 3%.
The braking load is too heavy.
•
Calculate the braking load and braking power again, and
decrease the braking load.
•
Use a braking resistor that improves braking power.
The braking resistor is not sufficient.
Use the braking resistor specifications to select a sufficient braking
resistor.
Note:
•
The drive detects this error if the braking resistor overheat protective function is active.
•
The magnitude of the braking load causes the braking resistor overheat alarm, NOT the surface temperature. If the duty cycle is higher than the braking resistor rating, the drive
will show the alarm.
•
Do a Fault Reset to clear the fault.
•
Parameter
L8-01
enables and disables
rH
detection.
Code
Name
Causes
Possible Solutions
rr
Dynamic Braking Transistor Fault
The drive control circuit is damaged.
There is a malfunction in the internal braking
transistor of the drive.
•
Re-energize the drive.
•
If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
SC
Short Circuit/IGBT Failure
Overheating caused damage to the motor or the motor
insulation is not satisfactory.
Measure the motor insulation resistance, and replace the motor if
there is electrical conduction or unserviceable insulation.
The motor main circuit cable is contacting ground to
make a short circuit.
•
Examine the motor main circuit cable for damage, and repair
short circuits.
•
Measure the resistance between the motor main circuit cable and
the ground terminal. If there is electrical conduction, replace the
cable.
A short circuit or ground fault on the drive output
side caused damage to the output transistor of the
drive.
•
Make sure that there is not a short circuit in terminal B1 and
terminals U/T1, V/T2, and W/T3. Make sure that there is not a
short circuit in terminals - and terminals U/T1, V/T2, and W/T3.
•
If there is a short circuit, contact Yaskawa or your nearest sales
representative.
When
A1-02 = 5, 6, 7 [Control Method Selection =
OLV/PM, AOLV/PM, or CLV/PM]
, the output current
is more than the value set in
L8-27 [Overcurrent
Detection Gain]
.
Set
L8-27
correctly.
Note:
•
The drive detects this error if there is a short circuit or ground fault on the drive output side, or an IGBT failure.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
SCF
Safety Circuit Fault
The safety circuit is broken.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
Note:
Do a Fault Reset to clear the fault.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...