YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
111
Code
Name
Causes
Possible Solutions
SEr
Speed Search Retries Exceeded
The speed search-related parameters are set
incorrectly.
•
Decrease
b3-10 [Speed Estimation Detection Gain]
.
•
Increase
b3-17 [Speed Est Retry Current Level]
.
•
Increase
b3-18 [Speed Est Retry Detection Time]
.
•
Do Auto-Tuning again.
The motor is coasting in the opposite direction of the
Run command.
Set
b3-14 = 1 [Bi-directional Speed Search = Enabled]
.
Note:
•
The drive detects this error if the number of speed search restarts is more than
b3-19 [Speed Search Restart Attempts]
.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
STPo
Motor Step-Out Detected
The motor code is set incorrectly for PM Control
Methods.
•
Set
E5-01 [PM Motor Code Selection]
correctly as specified by
the motor.
•
For specialized motors, refer to the motor test report and set
E5-
xx
correctly.
The load is too large.
•
Increase the value set in
n8-55 [Motor to Load Inertia Ratio]
.
•
Increase the value set in
n8-51 [Pull-in Current @ Acceleration]
.
If the drive detects
STPo
during deceleration when increasing the
value set in
n8-51
, set the value of
n8-79 [Pull-in Current @
Deceleration]
lower than
n8-51
.
•
Decrease the load.
•
Replace the drive and motor with larger capacity models.
The load inertia is too large.
Increase the value set in
n8-55
.
The acceleration/deceleration times are too short.
•
Increase the values set in
C1-01 to C1-08 [Acceleration/
Deceleration Times]
.
•
Increase the value set in
C2-01 [S-Curve Time @ Start of Accel]
.
Speed response is too slow.
Increase the value set in
n8-55
.
Note:
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
SvE
Zero Servo Fault
The value set in the torque limit is too small.
Adjust torque limit-related parameters
L7-01 to L7-04
.
The load torque is too large.
Decrease the load torque.
Noise interference along the encoder cable
Isolate the encoder cable from the drive output line or a different
source of electrical interference.
Note:
•
The drive detects this error if motor rotation position moves during Zero Servo.
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
TiM
Keypad Time Not Set
There is a battery in the keypad, but the date and time
are not set.
Use the keypad to set the date and time.
Note:
•
Do a Fault Reset to clear the fault.
•
Parameter
o4-24 [bAT Detection Selection]
enables and disables
TiM
detection.
Code
Name
Causes
Possible Solutions
UL3
Undertorque Detection 1
A fault occurred on the machine.
Example: There is a broken pulley belt.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load.
Adjust
L6-02 [Torque Detection Level 1]
and
L6-03 [Torque
Detection Time 1]
settings.
Note:
•
The drive detects this error if the drive output current is less than the level set in
L6-02
for longer than
L6-03
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this error, it will operate the motor as specified by the Stopping Method set in
L6-01 [Torque Detection Selection 1]
.
Code
Name
Causes
Possible Solutions
UL4
Undertorque Detection 2
A fault occurred on the machine.
Example: There is a broken pulley belt.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load.
Adjust
L6-05 [Torque Detection Level 2]
and
L6-06 [Torque
Detection Time 2]
settings.
Note:
•
The drive detects this error if the drive output current is less than the level set in
L6-05
for longer than
L6-06
.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this error, it will operate the motor as specified by the Stopping Method set in
L6-04 [Torque Detection Selection 2]
.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...