TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
No.
(Hex.)
Name
Description
Default
(Range)
L5-05
(0467)
Auto-Restart Method
Sets the count method for the Auto Restart operation.
0 : Continuous/Immediate Attempts
1 : Interval/Attempt after L5-04 sec
0
(0, 1)
L5-07
(0B2A)
Fault Reset Enable Select
Grp1
Use these 4 digits to set the Auto Restart function for
oL1
to
oL4
. From left to right, the digits set
oL1
,
oL2
,
oL3
, and
oL4
, in order.
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
1110 : Enabled (oL1/oL2/oL3/—)
1111 : Enabled (oL1/oL2/oL3/oL4)
1111
(0000 - 1111)
L5-08
(0B2B)
Fault Reset Enable Select
Grp2
Use these 4 digits to set the Auto Restart function for
Uv1
,
ov
,
oH1
, and
GF
. From left to right, the
digits set
Uv1
,
ov
,
oH1
, and
GF
, in order.
0000 : Disabled
0001 : Enabled (—/–/—/GF)
0010 : Enabled (—/–/oH1/–)
0011 : Enabled (—/–/oH1/GF)
0100 : Enabled (—/ov/—/–)
0101 : Enabled (—/ov/—/GF)
0110 : Enabled (—/ov/oH1/–)
0111 : Enabled (—/ov/oH1/GF)
1000 : Enabled (Uv1/–/—/–)
1001 : Enabled (Uv1/–/—/GF)
1010 : Enabled (Uv1/–/oH1/–)
1011 : Enabled (Uv1/–/oH1/GF)
1100 : Enabled (Uv1/ov/—/–)
1101 : Enabled (Uv1/ov/—/GF)
1110 : Enabled (Uv1/ov/oH1/–)
1111 : Enabled (Uv1/ov/oH1/GF)
1111
(0000 - 1111)
◆
L6: Torque Detection
No.
(Hex.)
Name
Description
Default
(Range)
L6-01
(04A1)
Torque Detection Selection 1
Sets torque detection conditions that will trigger an overtorque or undertorque response from the
drive.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
0
(0 - 8)
L6-02
(04A2)
Torque Detection Level 1
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
150%
(0 - 300%)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...