2.9 Diagnosing and Resetting Faults
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
137
2.9
Diagnosing and Resetting Faults
When a fault occurs and the drive stops, do the procedures in this section to remove the cause of the fault, then re-
energize the drive.
◆
Fault and Power Loss Occur at the Same Time
WARNING!
Crush Hazard. Wear eye protection when you do work on the drive. If you do not use correct safety equipment, it can
cause serious injury or death.
WARNING!
Electrical Shock Hazard. After the drive blows a fuse or trips a GFCI, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then
check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact
Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral
devices, it can cause serious injury or death.
1.
Supply power to the control circuit from the external 24 V input.
2.
Use monitor parameters
U2-xx [Fault Trace]
to show the fault code and data about the operating status of the
drive immediately before the fault occurred.
3.
Use the information in the Troubleshooting tables to remove the fault.
Note:
1. To find the faults that were triggered, check the fault history in
U2-02 [Previous Fault]
. To find information about drive status (such as
frequency, current, and voltage) when the faults were triggered, check
U2-03 to U2-20
.
2. If the fault display stays after you re-energize the drive, remove the cause of the fault and reset.
◆
Fault Occurs Without Power Loss
1.
Examine the fault code shown on the keypad.
2.
Use the information in the Troubleshooting tables to remove the fault.
3.
Do a fault reset.
◆
Fault Reset
If a fault occurs, you must remove the cause of the fault and re-energize the drive.
lists the different
methods to reset the drive after a fault.
Table 2.3 Fault Reset Methods
Methods
Description
Method 1
While the keypad is showing the fault or alarm code, push
(Reset) or
on the keypad.
Method 2
Switch ON the MFDI terminal set to
H1-xx = 14 [MFDI Function Select = Fault Reset]
.
Note:
The default setting for
H1-04 [Terminal S4 Function Selection]
is
14 [Fault Reset]
.
Method 3
1.
De-energize the drive main circuit power supply.
2.
Energize the drive again after the keypad display goes out.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...