3.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
274
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
No.
Name
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
L4-03
Speed Agree
Detection Level
(+/-)
-590.0 - +590.0
0.1
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
L4-04
Speed Agree
Detection Width
(+/-)
0.0 - 20.0
0.1
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
2.0 Hz
L8-38
Carrier Frequency
Reduction
0 - 2
1
-
L8-40
Carrier Freq
Reduction Off-
Delay
0.00 - 2.00
0.01 s
0.50
0.50
0.50
0.50
-
L8-90
STPo Detection
Level (Low
Speed)
0 - 5000
1
-
-
-
-
-
n1-15
PWM Voltage
Offset Calibration
0 - 2
1
1
1
1
1
2
n5-04
Speed Response
Frequency
0.00 - 500.00
0.01 Hz
-
-
-
50.00
50.00
n8-35
Initial Pole
Detection Method
0 - 2
1
-
-
-
-
-
n8-51
Pull-in Current @
Acceleration
0 - 200
1%
-
-
-
-
-
o1-03
Frequency
Display Unit
Selection
0 - 3
1
0
0
0
0
0
o1-04
V/f Pattern
Display Unit
0 - 1
1
-
-
-
0
0
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
*2
Models 2211 to 2415, 4103 to 4720, and T103 to T720 use these default settings when
C6-01 = 1 [Normal / Heavy Duty Selection =
Normal Duty Rating]
. Models 2257 to 2415, 4140 to 4720, and T103 to T720 use these default settings when
C6-01 = 0 [Heavy Duty
Rating]
.
•
A1-02 = 2 [Open Loop Vector]
: 2.00
•
A1-02 = 3, 4 [Closed Loop Vector, Advanced Open Loop Vector]
: 0.05
*3
The default setting changes when
C6-01 [Normal / Heavy Duty Selection]
changes.
*4
The maximum value changes when
A1-02
changes:
•
When
A1-02 = 0, 2 [V/f Control, Open Loop Vector]
, the maximum value is 590.0 Hz.
•
When
A1-02 = 1, 3 [V/f Control with Encoder, Closed Loop Vector]
, the maximum value is 400.0 Hz.
•
When
A1-02 = 4 [Advanced Open Loop Vector]
, the maximum value is 120.0 Hz.
*5
The default setting changes when the drive model and
E1-03 [V/f Pattern Selection]
change.
*6
This is the value for 200 V class drives. Double the value for 400 V class drives.
*7
The maximum value changes when
A1-02
changes:
•
When
A1-02 = 0, 2 [V/f Control, Open Loop Vector]
, the maximum value is 590.0 Hz.
•
When
A1-02 = 1 [V/f Control with Encoder]
, the maximum value is 400.0 Hz.
•
When
A1-02 = 4 [Advanced Open Loop Vector]
, the maximum value is 120.0 Hz.
*8
The minimum value changes when
A1-02
changes:
•
When
A1-02 = 0, 2 [V/f Control, Open Loop Vector]
, the minimum value is -590.0 Hz.
•
When
A1-02 = 1, 3 [V/f Control with Encoder, Closed Loop Vector]
, the minimum value is -400.0 Hz.
•
When
A1-02 = 4 [Advanced Open Loop Vector]
, the minimum value is -120.0 Hz.
◆
A1-02 = 5 to 8 [Control Method for PM Motors and EZ Vector Control]
No.
Name
Range
Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
EZOLV
(8)
b2-01
DC Injection/Zero
SpeedThreshold
0.0 - 10.0
0.1
0.5 Hz
1.0%
0.5%
0.5 Hz
b2-04
DC Inject Braking Time
at Stop
0.00 - 10.00
0.01 s
0.00
0.00
0.00
0.00
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...