508
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Checked
No.
Description
17
Set
F1-01 [Encoder 1 Pulse Count (PPR)] and F1-05 [Encoder 1 Rotation Selection]
.
18
Set
E5-11 [Encoder Z-Pulse Offset]
.
Checked
No.
Description
19
The keypad will show
“
Rdy
”
after starting to operate the motor.
20
To give the Run command and frequency reference from the keypad, push
to set to LOCAL Mode (when in LOCAL Mode, the LO/RE LED
illuminates).
21
If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
22
Set Heavy Duty or Normal Duty Mode with
C6-01 [Normal / Heavy Duty Selection]
to conform to the load condition.
23
Set
E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload Protection Select]
correctly for motor thermal protection.
24
Set the drive for REMOTE Mode when the control circuit terminals supply the Run command and frequency reference (in REMOTE Mode, the LO/
RE LED turns OFF).
25
When terminal A1 is used for the frequency reference:
•
Voltage input
–
Set DIP Switch S1-1 on the drive to
“
V
”
.
–
Set
H3-01 = 0, 1 [Terminal A1 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar Reference)]
.
–
Set
H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference]
.
•
Current input
–
Set DIP Switch S1-1 on the drive to
“
I
”
.
–
Set
H3-01 = 2, 3 [Terminal A1 Signal Level Select = 4 to 20 mA, 0 to 20 mA]
.
–
Set
H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference]
.
26
When terminal A2 is used for the frequency reference:
•
Voltage input
–
Set DIP Switch S1-2 on the drive to
“
V
”
.
–
Set
H3-09 = 0, 1 [Terminal A2 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to 10 V (Bipolar Reference)]
.
–
Set
H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference]
.
•
Current input
–
Set DIP Switch S1-2 on the drive to
“
I
”
.
–
Set
H3-09 = 2, 3 [Terminal A2 Signal Level Select = 4 to 20 mA, 0 to 20 mA]
.
–
Set
H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference]
.
27
When terminal A3 is used for the frequency reference:
•
Voltage input
–
Set DIP Switch S4 on the drive to analog input side.
–
Set DIP Switch S1-3 on the drive to
“
V
”
.
–
Set
H3-05 = 0, 1 [Terminal A3 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar Reference)]
.
–
Set
H3-06 = 0 [Terminal A3 Function Selection = Frequency Reference]
.
•
Current input
–
Set DIP Switch S4 on the drive to analog input side.
–
Set DIP Switch S1-3 on the drive to
“
I
”
.
–
Set
H3-05 = 2, 3 [Terminal A3 Signal Level Select = 4 to 20 mA (Lower Limit at 4), 0 to 20 mA (Bipolar Reference)]
.
–
Set H3-06 = 0 [Terminal A3 Function Selection = Frequency Reference].
28
Make sure that the frequency reference reaches the necessary minimum and maximum values.
→ If drive operation is incorrect, make these adjustments:
Gain adjustment: Set the maximum voltage and current values, then adjust the analog input gain until the frequency reference reaches the necessary
value. (For terminal A1 input:
H3-03
, for terminal A2 input:
H3-11
, for terminal A3 input:
H3-07
)
Bias adjustment: Set the maximum voltage/current values, then adjust the analog input bias until the frequency reference reaches the necessary
minimum value. (For terminal A1 input:
H3-04
, for terminal A2 input:
H3-12
, for terminal A3 input:
H3-08
)
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...