5.17
Wiring Checklist
Wire the drive, examine these items, then do a test run.
Table 5.27 Power Supply Voltage
Checked
No.
Item to Check
1
The power supply voltage must be in the input voltage specification range of the drive.
Table 5.28 Main Circuit Wiring
Checked
No.
Item to Check
1
•
Put the power supply through a molded-case circuit breaker (MCCB) before it gets to the drive input.
•
Connect an applicable MCCB.
2
Correctly wire the power supply to drive main circuit terminals R/L1, S/L2, T/L3, R1/L11, S1/L21, and T1/L31.
3
Correctly wire the drive and motor together.
The motor lines and drive output terminals must align to make the correct phase order.
Note:
If the phase order is incorrect, the drive will rotate in the opposite direction.
4
Use 600 V heat resistant indoor PVC wire for the power supply and motor lines.
Note:
Wire gauge recommendations assume use of 600 V class 2 heat-resistant indoor PVC wire.
5
Use the correct wire gauges for the main circuit.
Note:
•
When the wiring distance between the drive and the motor is long, use this formula for the voltage drop in the wire:
Motor rated voltage (V) × 0.02 ≥ √3 × wire resistance (Ω/km) × wiring distance (m) × motor rated current (A) × 10
-3
•
When the cable between the drive and motor is longer than 50 m (164 ft), use parameter
C6-02 [Carrier Frequency Selection]
to decrease the
carrier frequency.
6
Correctly ground the drive.
7
Tighten the main circuit and grounding terminal screws of the drive to a correct tightening torque.
8
When operating more than one motor from one drive, set up overload protection circuits.
A - Power Supply
B - Drive
C - oL1, oL2: Thermal overload relay
Note:
Set
H1-03 = 25 [Terminal S3 Function Selection = External Fault (NC-Always-Coast)]
.
9
When you use a braking resistor or a braking resistor unit, install an electromagnetic contactor (MC).
Correctly install the resistor and make sure that overload protection uses the MC to shut off the power supply.
10
Make sure you did not install phase advancing capacitors, input noise filters, or ELCBs, GFCIs, RCM/RCDs on the output side of the drive.
Table 5.29 Control Circuit Wiring
Checked
No.
Item to Check
1
Use twisted-pair cables for all drive control circuit wiring.
2
Ground the shields of shielded wiring to terminal E (G).
3
For 3-Wire sequence, set parameters for MFDI terminals and wire control circuits.
4
Correctly install any options.
5
Examine the drive for other wiring errors.
Only use a multimeter to check wiring.
6
Tighten the control circuit terminal screws of the drive to a correct tightening torque.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...