TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
389
*3
When you use an external 24 V power supply, the operation of the MFDO terminals are different for different drive software versions.
Note:
The
“
PRG
”
column on the nameplate on the right side of the drive identifies the software version. You can also use
U1-25 [SoftwareNumber
FLASH]
to identify the software version.
•
Drive software versions PRG: 09012 and later
When the main circuit power supply of the drive turns off, and you remove the cause of a fault and do a fault reset from the keypad, the
fault relay output terminals and the MFDO terminals set for
H2-xx = E, 10E [Fault]
will change status.
•
Drive software versions PRG: 09011 and earlier
When the main circuit power supply of the drive turns off, and you remove the cause of a fault and do a fault reset from the keypad, the
fault relay output terminals and the MFDO terminals set for
H2-xx = E, 10E [Fault]
will keep the same status as before the main circuit
power supply of the drive turned off, but the fault code shown on the keypad will disappear.
*4
If the motor shaft can rotate while the 24 V control power supply is energized and the main circuit power supply is de-energized, re-
energize the 24 V control power supply and energize the main circuit power supply.
*5
When you use an external 24 V power supply, the operation of the Analog Output option is different for different drive software versions.
On drives with software versions PRG:09015 and later, the Analog Output option (AO-A3) can output the analog signals.
Note:
The
“
PRG
”
column on the nameplate on the right side of the drive identifies the software version. You can also use
U1-25 [SoftwareNumber
FLASH]
to identify the software version.
When you use an external 24 V power supply, if you de-energize the main circuit power supply, the encoder option
will not operate, even when you connect the external 24 V power supply to terminals PS-AC. When you use an
encoder option, energize the drive main circuit power supply.
Note:
Yaskawa recommends that you use different external power supplies for the external power supply input terminals (PS-AC) and MFDI
selection common terminal (SC) / Input signal common terminal (SC).
Wiring MFDI Terminals
If you de-energize the main circuit power supply, the MFDI terminals will not operate, even when you connect the
external 24 V power supply to terminals PS-AC. When you set N.O. functions to
H1-xx [MFDI Function Select]
,
MFDI terminals always deactivate. When you set N.C. functions, MFDI terminals always activate. Connect the
external 24 V power supply to the MFDI selection common terminal (SC).
A - External power supply
Figure 5.48 Wiring MFDI Terminals
Wiring Digital Input Option (DI-A3)
If you de-energize the main circuit power supply, the Digital Input Option terminals will not operate, even when you
connect the external 24 V power supply to terminals PS-AC. When you set N.O. functions to
F3-xx [Terminal Dx
Function Selection]
, the input terminals on the digital input option always deactivate. When you set N.C. functions,
the input terminals on the digital input option always activate. Connect the external 24 V power supply to the Input
signal common terminal (SC).
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...