496
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Auto-Tuning Type
Mode
Multi-Function Input
Digital Output
ASR and Inertia Tuning
Rotational
Inertia Tuning
Disabled
Functions the same as during usual
operation.
ASR (Speed Regulator)
Disabled
Functions the same as during usual
operation.
Deceleration Rate Tuning
Disabled
Functions the same as during usual
operation.
KEB Tuning
Disabled
Functions the same as during usual
operation.
WARNING!
Crush Hazard. Wire a sequence that will not let a multi-function output terminal open the holding brake during
Stationary Auto-Tuning. If the holding brake is open during Stationary Auto-Tuning, it can cause serious injury or death.
WARNING!
Sudden Movement Hazard. Before you do Rotational Auto-Tuning, disconnect the load from the motor. The load can
move suddenly and cause serious injury or death.
WARNING!
Injury to Personnel. Rotational Auto-Tuning rotates the motor at 50% or more of the motor rated frequency. Make sure
that there are no issues related to safety in the area around the drive and motor. Increased motor frequency can cause serious
injury or death.
WARNING!
Electrical Shock Hazard. During Auto-Tuning, the motor will receive high voltage when the motor is stopped. Do not
touch the motor until Auto-Tuning is complete. If you touch a motor that is energized, it can cause serious injury or death.
■
Precautions before Rotational Auto-Tuning
WARNING!
Electrical Shock Hazard. During Auto-Tuning, the motor will receive high voltage when the motor is stopped. Do not
touch the motor until Auto-Tuning is complete. If you touch a motor that is energized, it can cause serious injury or death.
•
Before you do Rotational Auto-Tuning to prevent drive malfunction, uncouple the motor from the load. If you do
Rotational Auto-Tuning with the motor connected to a load that is more than 30% of the motor duty rating, the
drive will not correctly calculate the motor parameters and the motor can operate incorrectly.
•
When the load is 30% or less of the motor duty rating, you can do Auto-Tuning with the motor connected to a load.
•
Make sure that the motor magnetic brake is released.
•
Make sure that external force from the machine will not cause the motor to rotate.
■
Precautions before Stationary Auto-Tuning
•
Make sure that the motor magnetic brake is not open.
•
Make sure that external force from the machine will not cause the motor to rotate.
WARNING!
Electrical Shock Hazard. During Auto-Tuning, the motor will receive high voltage when the motor is stopped. Do not
touch the motor until Auto-Tuning is complete. If you touch a motor that is energized, it can cause serious injury or death.
Automatically Set E2-02 [Motor Rated Slip] and E2-03 [Motor No-Load Current]
If
T1-12 = 1 [Test Mode Selection = Yes]
when selecting Stationary Auto-Tuning, the drive will automatically set
motor parameters
E2-02 [Motor Rated Slip]
and
E2-03 [Motor No-Load Current]
after Auto-Tuning is complete
when you use the motor for the first time in Drive Mode.
After Stationary Auto-Tuning is complete, use this procedures to do the operation in test mode:
1. Check the
E2-02
and
E2-03
values on the
“
Modified Parameters/Fault Log
”
screen or the
“
Parameters
”
screen.
2. Operate the motor in Drive Mode with these conditions:
•
Make sure that you connect all wiring between the drive and motor
•
Make sure that a mechanical brake on the motor shaft is not locked
•
The maximum motor load must be 30% of the rated load.
•
Keep a constant speed of 30% of
E1-06 [Base Frequency]
(default value = maximum frequency) or more for 1
second or longer.
3. After the motor stops, check the
E2-02
and
E2-03
values on the
“
Modified Parameters/Fault Log
”
screen or the
“
Parameters
”
screen again.
4. Make sure that the input data is correct.
When the settings in
E2-02
and
E2-03
are different than in step 1, the drive set the values automatically.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...