5.15 Short Circuit Protection Requirements for UL Listing
420
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Protected Enclosure Not Required
Ventilated Protected Enclosure Required
Drive
Catalog
Code
GA80U
Semiconductor Fuse
Part Number
Manufacturer: Eaton/
Bussman
Class CC, J or T Fuse
Maximum Amps
MCCB
Maximum Amps
Class RK1
or RK5 Fuse
Maximum
Amps
Enclosure Volume
Minimum (in
3
)
2006
FWH-45B
10
15
10
4195
2008
FWH-45B
12
15
12
4195
2010
FWH-45B
15
15
15
4195
2012
FWH-50B
or FWH-80B
20
20
20
4195
2018
FWH-80B
or FWH-100B
30
35
30
4195
2021
FWH-80B
or FWH-100B
35
40
35
4195
2030
FWH-100B
or FWH-125B
50
60
50
4195
2042
FWH-150B
70
80
70
4195
2056
FWH-200B
90
110
90
4195
2070
FWH-200B
or FWH-225A
110
125
110
4195
2082
FWH-225A
or FWH-250A
125
150
125
4195
2110
FWH-225A
or FWH-250A
175
200
175
10121
2138
FWH-275A
or FWH-300A
225
250
225
10121
2169
FWH-275A
or FWH-350A
250
300
250
10121
2211
FWH-325A
or FWH-450A
350
400
350
10121
2257
FWH-600A
400
500
400
14657
2313
FWH-700A
or FWH-800A
500
600
500
14657
2360
FWH-800A
or FWH-1000A
600
700
600
52800
2415
FWH-1000A
700
800
n/a
52800
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...