Code
Name
Causes
Possible Solutions
Er-12
Current Detection Error
There is a phase loss in the drive input power. (U/T1,
V/T2, W/T3)
Examine and repair motor wiring.
The current exceeded the current rating of the drive.
The output current is too low.
•
Check the motor wiring for any short circuits between the wires.
•
Check and turn ON any magnetic contactors used between
motors.
•
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest
sales representative.
You tried Auto-Tuning without a motor connected to
the drive.
Connect the motor and do Auto-Tuning.
There was a current detection signal error.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
Code
Name
Causes
Possible Solutions
Er-13
Leakage Inductance Alarm
The motor rated current value is incorrect.
Correctly set the rated current indicated on the motor nameplate and
perform Auto-Tuning again.
The drive could not complete tuning for leakage
inductance in fewer than 300 seconds.
Examine and repair motor wiring.
Code
Name
Causes
Possible Solutions
Er-14
Motor Speed Error 2
The motor speed was more than two times the
amplitude of speed reference during Inertia Tuning.
Decrease the value set in
C5-01 [ASR Proportional Gain 1]
.
Code
Name
Causes
Possible Solutions
Er-15
Torque Saturation Error
During Inertia Tuning, the output torque was more
than the value set in
L7-01 to L7-04 [Torque Limit]
.
•
Increase the value set in
L7-01 to L7-04 [Torque Limit]
as much
as possible.
•
Decrease the values set for the frequency and amplitude of the
test signals used when doing inertia tuning. First, decrease the
test signal amplitude, and then do Inertia Tuning. If the error
continues, decrease the test signal frequency and do Inertia
Tuning again.
Code
Name
Causes
Possible Solutions
Er-16
Inertia ID Error
The inertia found by the drive was too small or too
large during Inertia Tuning (10% or less, or 50000%
or more).
•
Decrease the values set for the frequency and amplitude of the
test signals used when doing inertia tuning. First, decrease the
test signal amplitude, and then do Inertia Tuning. If the error
continues, decrease the test signal frequency and do Inertia
Tuning again
•
Correctly set the motor inertia as specified by the motor, and do
Inertia Tuning again.
Code
Name
Causes
Possible Solutions
Er-17
Reverse Prohibited Error
b1-04 = 1 [Reverse Operation Selection = Reverse
Disabled]
Note:
You cannot do Inertia Tuning if the drive cannot
rotate the motor in reverse.
1.
Enable reverse in the target machine.
2.
Set
b1-04 = 0 [Reverse Enabled]
.
3.
Do Inertia Tuning again.
Code
Name
Causes
Possible Solutions
Er-18
Back EMF Error
The result of the induced voltage tuning was not in
the applicable range.
1.
Make sure that the input motor nameplate data is correct.
2.
Do Auto-Tuning again and correctly set the motor nameplate
data.
Code
Name
Causes
Possible Solutions
Er-19
PM Inductance Error
The Auto-Tuning results of the PM motor inductance
were not in the applicable range.
1.
Make sure that the input motor nameplate data is correct.
2.
Do Auto-Tuning again and correctly set the motor nameplate
data.
Code
Name
Causes
Possible Solutions
Er-20
Stator Resistance Error
The Auto-Tuning results of the PM Motor Stator
Resistance were not in the applicable range.
1.
Make sure that the input motor nameplate data is correct.
2.
Do Auto-Tuning again and correctly set the motor nameplate
data.
Code
Name
Causes
Possible Solutions
Er-21
Z Pulse Correction Error
The motor is wired incorrectly.
The encoder is wired incorrectly.
1.
Repair motor and encoder wiring errors.
2.
Do Z Pulse Offset Tuning again.
You did Auto-Tuning on a coasting motor.
1.
Wait for the motor to fully stop.
2.
Do Z Pulse Offset Tuning again.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...