130
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
2.7
Auto-Tuning Errors
This table gives information about errors detected during Auto-Tuning. If the drive detects an Auto-Tuning error, the
keypad will show the error and the motor will coast to stop. The drive will not send notification signals for faults and
alarms when Auto-Tuning errors occur.
Two types of Auto-Tuning errors are:
Endx
and
Erx
.
Endx
identifies that Auto-Tuning has successfully completed
with calculation errors. Find and repair the cause of the error and do Auto-Tuning again, or set the motor parameters
manually. You can use the drive in the application if you cannot find the cause of the
Endx
error.
Erx
identifies that Auto-Tuning was not successful. Find and repair the cause of the error and do Auto-Tuning again.
Code
Name
Causes
Possible Solutions
End1
Excessive Rated Voltage Setting
The torque reference was more than 20% during
Auto-Tuning or the no-load current that was
measured after Auto-Tuning is more than 80%.
•
Make sure that the input motor nameplate data is correct.
•
Do Auto-Tuning again and correctly set the motor nameplate
data.
•
If you can uncouple the motor and load, remove the motor from
the machine and do Rotational Auto-Tuning again.
•
If you cannot uncouple the motor and load, use the results from
Auto-Tuning.
Code
Name
Causes
Possible Solutions
End2
Iron Core Saturation Coefficient
The motor nameplate data entered during Auto-
Tuning is incorrect.
•
Make sure that the input motor nameplate data is correct.
•
Do Auto-Tuning again and correctly set the motor nameplate
data.
Auto-Tuning results were not in the applicable
parameter setting range, and
E2-07
or
E2-08 [Motor
Saturation Coefficient 2]
have temporary values.
•
Examine and repair damaged motor wiring.
•
If you can uncouple the motor and load, remove the motor from
the machine and do Rotational Auto-Tuning again.
Code
Name
Causes
Possible Solutions
End3
Rated Current Setting Alarm
The rated current value is incorrect.
Do Auto-Tuning again and set the correct rated current shown on the
motor nameplate.
Code
Name
Causes
Possible Solutions
End4
Adjusted Slip Calculation Error
The Auto-Tuning results were not in the applicable
parameter setting range.
The motor rated slip that was measured after
Stationary Auto-Tuning was 0.2 Hz or lower.
The motor rated slip that was measured after
compensation with
E2-08 [Motor Saturation
Coefficient 2]
is not in the applicable range.
The secondary resistor measurement results were not
in the applicable range.
•
Make sure the input motor nameplate data is correct.
•
Do Rotational Auto-Tuning again and correctly set the motor
nameplate data.
•
If you cannot uncouple the motor and load, do Stationary Auto-
Tuning 2.
Code
Name
Causes
Possible Solutions
End5
Resistance Tuning Error
The Auto-Tuning results of the Line-to-Line
Resistance were not in the applicable range.
•
Make sure that the input motor nameplate data is correct.
•
Examine and repair damaged motor wiring.
Code
Name
Causes
Possible Solutions
End6
Leakage Inductance Alarm
The Auto-Tuning results were not in the applicable
parameter setting range.
Make sure that the input motor nameplate data is correct, and do
Auto-Tuning again.
A1-02 [Control Method Selection]
setting is not
applicable.
•
Examine the value set in
A1-02
.
•
Make sure that the input motor nameplate data is correct, and do
Auto-Tuning again.
Code
Name
Causes
Possible Solutions
End7
No-Load Current Alarm
The Auto-Tuning results of the motor no-load current
value were not in the applicable range.
Examine and repair damaged motor wiring.
Auto-Tuning results were less than 5% of the motor
rated current.
Make sure that the input motor nameplate data is correct, and do
Auto-Tuning again.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...