7.6
Drive Specifications
Note:
•
To get the OLV, CLV, and AOLV specifications, do Rotational Auto-Tuning.
•
To get the longest product life, install the drive in an environment that meets the necessary specifications.
Table 7.11 Control Characteristics
Item
Specification
Control Methods
•
V/f Control
•
V/f Control with Encoder
•
Open Loop Vector
•
Closed Loop Vector
•
Advanced Open Loop Vector
•
PM Open Loop Vector
•
PM Advanced Open Loop Vector
•
PM Closed Loop Vector
•
EZ Vector Control
Carrier Frequency
•
Models 2004 to 2138, 4002 to 4103, and T103
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
•
Models 2169 to 2415, 4140 to 4414, and T140 to T414
HD: 5 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 10 kHz maximum.
•
Models 4477 to 4720, and T477 to T720
HD: 2 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 5 kHz maximum.
Maximum Output
Voltage
•
200 V Class: Three-phase 200 V to 240 V
•
400 V Class: Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Frequency Control
Range
•
AOLV and EZOLV: 0.01 Hz to 120 Hz
•
CL-V/f, CLV, AOLV/PM, and CLV/PM: 0.01 Hz to 400 Hz
•
V/f, OLV, and OLV/PM: 0.01 Hz to 590 Hz
Frequency Accuracy
(Temperature
Fluctuation)
Digital inputs: ±0.01% of the maximum output frequency (-10 °C to +40 °C (14 °F to 104 °F))
Analog inputs: In ±0.1% of the maximum output frequency (25 °C ±10 °C (77 °F ±18 °F))
Frequency Setting
Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output frequency (11-bit signed)
Output Frequency
Resolution
0.001 Hz
Frequency Setting
Signal
Main speed frequency reference: -10 Vdc to +10 Vdc (20 kΩ), 0 Vdc to 10 Vdc (20 kΩ), 4 mA to 20 mA (250 Ω), 0 mA to 20 mA (250 Ω)
Main speed reference: Pulse train input (maximum 32 kHz)
Starting Torque
•
V/f: 150%/3 Hz
•
CL-V/f: 150%/3 Hz
•
OLV: 200%/0.3 Hz
•
CLV: 200%/0 min
-1
(r/min)
•
AOLV: 200%/0.3 Hz
•
OLV/PM: 100%/5% speed
•
AOLV/PM: 200%/0 min
-1
(r/min)
•
CLV/PM: 200%/0 min
-1
(r/min)
•
EZOLV: 100%/1% speed
Note:
•
Correctly select the drive and motor capacity for this starting torque in these control methods:
–
OLV
–
CLV
–
AOLV
–
AOLV/PM
–
CLV/PM
•
Set
n8-57 = 1 [HFI Overlap Selection = Enabled]
for this starting torque in AOLV/PM. When you use a non-Yaskawa PM motor, do Rotational Auto-
Tuning.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...