YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
507
6.11
Test Run Checklist
Examine the items in this checklist and check each item before a test run.
Checked
No.
Description
1
Correctly install and wire the drive as specified by this manual.
2
Energize the drive.
3
Set the voltage for the power supply in
E1-01 [Input AC Supply Voltage]
.
Check the applicable items as specified by your control method.
WARNING!
Sudden Movement Hazard. Correctly wire the start/stop and safety circuits before you energize the drive. If you
momentarily close a digital input terminal, it can start a drive that is programmed for 3-Wire control and cause serious injury or death
from moving equipment.
Table 6.25 V/f Control [A1-02 = 0] and Closed Loop V/f Control [A1-02 = 1]
Checked
No.
Description
4
Select the best V/f pattern for your application and motor characteristics.
Example: For a motor with a rated frequency of 60 Hz, set
E1-03 = 1 [V/f Pattern Selection = Const Trq, 60Hz base, 60Hz max]
as a standard V/f
pattern.
Table 6.26 Closed Loop V/f Control [A1-02 = 1]
Checked
No.
Description
5
Set
F1-01 [Encoder 1 Pulse Count (PPR)]
correctly and make sure that encoder pulse counting direction is correct.
6
Set
C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1]
.
Table 6.27 Open Loop Vector Control [A1-02 = 2] or Closed Loop Vector Control [A1-02 = 3]
Checked
No.
Description
7
Decouple motor shafts and machines.
8
Refer to the information on the motor nameplate and set this data correctly:
•
Motor rated power (kW) to
T1-02
•
Motor rated voltage (V) to
T1-03
•
Motor rated current (A) to
T1-04
•
Motor base frequency (Hz) to
T1-05
•
Number of motor poles to
T1-06
•
Motor base speed (min
-1
) to
T1-07
9
Do Rotational Auto-Tuning.
Table 6.28 Closed Loop Vector Control [A1-02 = 3]
Checked
No.
Description
10
Set
F1-01 [Encoder 1 Pulse Count (PPR)] and F1-05 [Encoder 1 Rotation Selection]
.
11
Set
C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1]
.
Table 6.29 PM Open Loop Vector Control [A1-02 = 5]
Checked
No.
Description
12
Set
E5-01 through E5-24 [PM Motor Settings]
.
Table 6.30 PM Advanced Open Loop Vector [A1-02 = 6]
Checked
No.
Description
13
Set
E5-01 through E5-24 [PM Motor Settings]
.
14
Set
C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1]
.
Table 6.31 PM Closed Loop Vector Control [A1-02 = 7]
Checked
No.
Description
15
Set
E5-01 through E5-24 [PM Motor Settings]
.
16
Set
C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1]
.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...