YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
387
Table 5.8 Control Circuit Output Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Fault Relay
Output
MA
N.O. output
(Fault)
•
Relay output
•
30 Vdc, 10 mA to 1 A
•
250 Vac, 10 mA to 1 A
•
Minimum load: 5 V, 10 mA (Reference value)
MB
N.C. output
(Fault)
MC
Digital output common
MFDO
M1
MFDO
(During Run)
•
Relay output
•
30 Vdc, 10 mA to 1 A
•
250 Vac, 10 mA to 1 A
•
Minimum load: 5 V, 10 mA (Reference value)
Note:
Do not set functions that frequently switch ON/OFF to MFDO (M1 to M6) because this will
decrease the performance life of the relay contacts. Yaskawa estimates switching life at
200,000 times (assumes 1 A, resistive load).
M2
M3
MFDO
(Zero Speed)
M4
M5
MFDO
(Speed Agree 1)
M6
Table 5.9 Control Circuit Monitor Output Terminals
Type
Terminal
Name (Default)
Function (Signal Level)
Monitor Output
MP
Pulse train output
(Output frequency)
32 kHz (maximum)
Refer to
“
Pulse Train Output
”
(page
) for more information.
FM
Analog monitor output 1
(Output frequency)
Select voltage or current output.
•
0 V to 10 V/0% to 100%
•
-10 V to +10 V/-100% to +100%
•
4 mA to 20 mA (Receiver recommended impedance: 250 Ω)
Note:
Select with jumper switch S5 and
H4-07 [Terminal FM Signal Level Select]
or
H4-08
[Terminal AM Signal Level Select]
.
AM
Analog monitor output 2
(Output current)
AC
Monitor common
0 V
■
External Power Supply Input Terminals
Refer to
for a list of the functions of the external power supply input terminals.
Table 5.10 External Power Supply Input Terminals
Type
Terminal
Name (Default)
Function
External Power Supply Input
Terminals
PS
External 24 V power supply input
Supplies backup power to the drive control circuit, keypad, and option board.
21.6 VDC to 26.4 VDC, 700 mA
AC
External 24 V power supply ground
0 V
Alarm Display When You Use External 24 V Power Supply
When you use an external 24 V power supply, the drive detects an alarm as shown in
if you set
o2-23
[External 24V Powerloss Detection]
and
o2-26 [Alarm Display at Ext. 24V Power]
for the main circuit power supply.
Set the alarm display as necessary.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...