YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
331
■
F4-03: Terminal V2 Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F4-03
(0393)
Terminal V2 Function
Selection
Sets the monitor signal output from terminal V2.
103
(000 - 999)
Set the x-xx part of the
Ux-xx [Monitors]
to set monitor data to output from the option card. For example, set
F4-03 =
103
to monitor
U1-03 [Output Current]
.
Note:
•
You cannot use all of the monitors in all of the control methods.
•
When you use the terminal in through mode, set this parameter to
000
or
031
. You can use this setting to adjust the V2 terminal output from
PLC through MEMOBUS/Modbus communications or a communications option.
■
F4-04: Terminal V2 Gain
No.
(Hex.)
Name
Description
Default
(Range)
F4-04
(0394)
RUN
Terminal V2 Gain
Sets the gain of the monitor signal that is sent from terminal V2. Sets the analog signal output level
from terminal V2 at 10 V or 20 mA as 100% when an output for monitoring items is 100%.
50.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V2 is ±10 V. Use
F4-08 [Terminal V2 Signal Level]
to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage of
terminal V2 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V2 outputs a
maximum voltage of 10 V.
•
F4-03 [Terminal V2 Function Selection] = 103 (U1-03: Output Current)
•
F4-04 = 50.0%
•
F4-06 [Terminal V2 Bias] = 0.0%
•
F4-08 = 0 (0 V to 10 V)
■
F4-05: Terminal V1 Bias
No.
(Hex.)
Name
Description
Default
(Range)
F4-05
(0395)
RUN
Terminal V1 Bias
Sets the bias of the monitor signal that is sent from terminal V1. When an output for monitoring
items is 0%, this parameter sets the analog signal output level from the V1 terminal as a percentage
of 10 V or 20 mA.
0.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V1 is ±10 V. Use
F4-07 [Terminal V1 Signal Level]
to set the
signal level.
■
F4-06: Terminal V2 Bias
No.
(Hex.)
Name
Description
Default
(Range)
F4-06
(0396)
RUN
Terminal V2 Bias
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog signal
sent from the V2 terminal at 10 V or 20 mA as 100% when an output for monitoring items is 0%.
0.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V2 is ±10 V. Use
F4-08 [Terminal V2 Signal Level]
to set the
signal level.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV