326
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Note:
•
Refer to
H1-xx
“
Multi-function Digital Input Setting Values
”
for more information about MFDI setting values.
•
Values
0 [3-Wire Sequence]
and
20 to 2F [External Fault]
for
F3-10 to F3-25
.
•
When you do not use DI-A3 as an MFDI, set
F3-10 to F3-25 = F [Not Used]
.
•
The drive reads DI-A3 terminal Dx two times as specified by parameter
b1-06 [Digital Input Reading]
.
•
Configuring such that
F3-01 = 8
when DI-A3 is the frequency reference source (
b1-01 or b1-15 = 3 [Frequency Reference Selection 1/2 =
Option PCB]
) results in the detection of
oPE05 [Run Cmd/Freq Ref Source Sel Err]
.
•
You can use these functions with the DI-A3 MFDI:
–
H1-40 to H1-42 [Mbus Reg 15C0h bit0 to bit2 Input Func]
–
H7-01 to H7-04 [Virtual Multi-Function Input 1 to 4]
■
F3-01: Digital Input Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-01
(0390)
Digital Input Function
Selection
Sets the data format of digital input signals. This parameter is enabled when
o1-03 = 0 or 1
[Frequency Display Unit Selection = 0.01 Hz or 0.01% (100% = E1-04)]
.
8
(0 - 8)
Note:
The input signal type is BCD when
o1-03 = 2 or 3 [Revolutions Per Minute (RPM) or User Units (o1-10 & o1-11)]
. The
o1-03
value sets the
setting units.
0 : BCD, 1% units
1 : BCD, 0.1% units
2 : BCD, 0.01% units
3 : BCD, 1 Hz units
4 : BCD, 0.1 Hz units
5 : BCD, 0.01 Hz units
6 : BCD (5-digit), 0.01 Hz
7 : Binary input
The setting unit and setting range vary depending on the value set in
F3-03 [Digital Input Data Length Select]
.
•
F3-03 = 0 [8-bit]
: 100%/255 (-255 to +255)
•
F3-03 = 1 [12-bit]
: 100%/4095 (-4095 to +4095)
•
F3-03 = 2 [16-bit]
: 100%/30000 (-33000 to +33000)
8 : Multi-Function Digital Input
The DI-A3 card is also used as a multi-function digital input terminal.
■
F3-03: Digital Input Data Length Select
No.
(Hex.)
Name
Description
Default
(Range)
F3-03
(03B9)
Digital Input Data Length
Select
Sets the number of bits to set the frequency reference with
DI-A3
.
2
(0 - 2)
0 : 8-bit
1 : 12-bit
2 : 16-bit
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV