1.22 Parameters Changed by PM Motor Code Selection
156
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
No.
Name
Unit
Motor Code (setting value of E5-01)
E1-09
Minimum Output
Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm
2
0.0017
0.0023
0.0043
0.0083
0.0136
0.017
0.027
0.046
L3-24
Motor Accel Time @
Rated Torque
s
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
n5-02
Motor Inertia
Acceleration Time
s
0.098
0.071
0.066
0.087
0.085
0.072
0.084
0.096
n8-49
Heavy Load Id Current
%
-6.6
-10.9
-13.5
-9.0
-9.5
-10.1
-6.0
-9.3
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
Table 1.12 SSR1 Series Motor Code Setting for Specification of 200 V at 1450 min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-01
PM Motor Code Selection
-
130E
130F
1310
1312
1313
1314
1315
Voltage Class
V
200
200
200
200
200
200
200
Capacity
kW
15
18
22
30
37
45
55
Motor Rotation Speed
min
-1
1450
1450
1450
1450
1450
1450
1450
E5-02
PM Motor Rated Power
kW
15.00
18.50
22.00
30.00
37.00
45.00
55.00
E5-03
PM Motor Rated Current
(FLA)
A
55.5
65.6
75.1
105.2
126.0
153.1
186.5
E5-04
PM Motor Pole Count
-
6
6
6
6
6
6
6
E5-05
PM Motor Resistance
(ohms/phase)
Ω
0.075
0.057
0.041
0.034
0.023
0.015
0.012
E5-06
PM d-axis Inductance (mH/
phase)
mH
3.29
2.53
1.98
1.75
1.48
1.04
0.87
E5-07
PM q-axis Inductance (mH/
phase)
mH
3.84
3.01
2.60
2.17
1.70
1.31
1.10
E5-09
PM Back-EMF Vpeak
(mV/(rad/s))
mVs/rad
311.2
300.9
327.7
354.2
369.6
351.6
374.7
E5-24
PM Back-EMF L-L Vrms
(mV/rpm)
mV/min
-1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Output Voltage
V
190.0
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Minimum Output
Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm
2
0.055
0.064
0.116
0.140
0.259
0.312
0.42
L3-24
Motor Accel Time @ Rated
Torque
s
0.085
0.080
0.122
0.108
0.161
0.160
0.175
n5-02
Motor Inertia Acceleration
Time
s
0.085
0.080
0.122
0.108
0.161
0.160
0.175
n8-49
Heavy Load Id Current
%
-10.7
-13.2
-15.7
-11.5
-7.0
-11.8
-10.2
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
Table 1.13 SSR1 Series Motor Code Setting for Specification of 400 V at 1450 min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-01
PM Motor Code
Selection
-
1332
1333
1335
1336
1338
133A
133B
133D
Voltage Class
V
400
400
400
400
400
400
400
400
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
Motor Rotation Speed
min
-1
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
PM Motor Rated Power
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11.0