YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
197
■
b1-03: Stopping Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-03
(0182)
Stopping Method Selection
Sets the method to stop the motor after removing a Run command or entering a Stop command.
0
(0 - 3)
Note:
When
A1-02 = 3, 4, 5, 6, 7, 8 [Control Method Selection = CLV, AOLV, OLV/PM, AOLV/PM, CLV/PM, EZOLV]
, the setting range is 0, 1, 3.
Select the applicable stopping method for the application from these four options:
0 : Ramp to Stop
When you enter the Stop command or turn OFF the Run command, the drive ramps the motor to stop.
The drive ramps the motor to stop as specified by the deceleration time. The default setting for the deceleration time
is
C1-02 [Deceleration Time 1]
. The actual deceleration time changes as the load conditions change (for example,
mechanical loss and inertia).
If the output frequency is less than or equal to the value set in
b2-01 [DC Injection/Zero SpeedThreshold]
during
deceleration, the drive will do DC Injection Braking, Zero Speed Control, or Short Circuit Braking, as specified by
the control method.
•
Ramp to Stop with V/f, AOLV, CL-V/f, and OLV Control Methods
Parameter
b2-01
sets the frequency to start DC Injection Braking at stop. If the output frequency is less than or
equal to the value set in
b2-01
during deceleration, then the drive will perform DC Injection Braking for the time set
in
b2-04 [DC Inject Braking Time at Stop]
.
Figure 2.10 Ramp to Stop with V/f, AOLV, CL-V/f, and OLV Control Methods
Note:
When
b2-01 ≤ E1-09 [Minimum Output Frequency]
, the drive will start DC Injection Braking from the frequency set in
E1-09
.
•
Ramp to Stop with OLV/PM, AOLV/PM, and EZOLV Control Methods
Parameter
b2-01
sets the frequency to start Short Circuit Braking. When the output frequency is less than or equal
to the value set in
b2-01
during deceleration, then the drive will do Short Circuit Braking for the time set in
b2-13
[Short Circuit Brake Time @ Stop]
. When
b2-04 ≠ 0
, the drive will do DC Injection Braking for the time set in
b2-
04
when Short Circuit Braking is complete.
Figure 2.11 Ramp to Stop with OLV/PM, AOLV/PM, and EZOLV Control Methods
Note:
When
b2-01 ≤ E1-09
, the drive will start Short Circuit Braking from the frequency set in
E1-09
.
If
b2-01 = 0 Hz
and
E1-09 = 0 Hz
, the drive will not do Short Circuit Braking.
•
Ramp to Stop in CLV and CLV/PM Control Methods
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...