290
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Operating Conditions
Speed limit
direction
+ (Positive)
- (Negative)
- (Negative)
+ (Positive)
+ (Positive)
- (Negative)
- (Negative)
+ (Positive)
Direction of motor
rotation
Forward
Reverse
Forward
Reverse
Generated torque
(d5-08 = 0
[Disabled])
Generated torque
(d5-08 = 1
[Enabled])
Application
example
*1
The
C5 parameter
set the Δn value.
■
Show Speed Limit Operation
When the motor is at the speed limit or more than the speed limit, the drive sends a signal to the PLC or other such
control devices to tell you that an error has occurred. To enable this function, set an MFDO function
[H2-01 to H2-
03]
to
32 [In Speed Limit During Trq Ctrl]
.
■
Switch Between Torque Control and Speed Control
Use a digital input to switch Torque Control and Speed Control. To enable this function, set
H1-xx = 71 [MFDI
Function Select = Torque Control]
to enable this function.
When you switch from Speed Control to Torque Control, the torque limit becomes the torque reference and the speed
reference becomes the speed limit. When you switch from Torque Control to Speed Control, the torque reference
becomes the torque limit and the speed limit becomes the speed reference. When you must use a delay time to switch
between Speed Control and Torque Control, set
d5-06 [Speed/Torque Changeover Time]
. During this switch delay
time, the drive keeps the reference value of the Torque Control and Speed Control when the switch signal was input.
Change the reference values from an external control device during this delay time.
Note:
•
When you switch between Torque Control and Speed Control, set
d5-01 = 0 [Torque Control Selection = Speed Control]
. If
d5-01 = 1
[Torque Control]
and
H1-xx = 71
at the same time, the drive will detect
oPE15 [Torque Control Setting Error]
.
•
If the Stop command is input, the drive will not apply the delay time set in
d5-06
. Torque Control will immediately switch to Speed Control
and ramp to stop.