1.22 Parameters Changed by PM Motor Code Selection
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
167
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-24
PM Back-EMF L-L
Vrms (mV/rpm)
mV/min
-1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Output
Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Minimum Output
Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm
2
0.0016
0.0022
0.0081
0.0133
0.0133
0.017
0.027
0.044
L3-24
Motor Accel Time @
Rated Torque
s
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
n5-02
Motor Inertia
Acceleration Time
s
0.092
0.068
0.125
0.139
0.083
0.070
0.082
0.092
n8-49
Heavy Load Id Current
%
-9.5
-9.4
-13.7
-10.0
-12.9
-19.9
-22.8
-19.8
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
Table 1.29 SST4 Series Motor Code Setting for Specification of 400 V at 1450 min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-01
PM Motor Code
Selection
-
233E
233F
2340
2342
2343
2344
2345
2346
Voltage Class
V
400
400
400
400
400
400
400
400
Capacity
kW
15
18
22
30
37
45
55
75
Motor Rotation Speed
min
-1
1450
1450
1450
1450
1450
1450
1450
1450
E5-02
PM Motor Rated Power
kW
15
18.50
22.00
30.00
37.00
45.00
55.00
75.00
E5-03
PM Motor Rated Current
(FLA)
A
27.1
34.2
37.6
50.9
65.4
80.2
96.1
129.2
E5-04
PM Motor Pole Count
-
6
6
6
6
6
6
6
6
E5-05
PM Motor Resistance
(ohms/phase)
Ω
0.291
0.220
0.192
0.136
0.091
0.064
0.048
0.028
E5-06
PM d-axis Inductance
(mH/phase)
mH
11.77
8.94
8.32
6.68
5.30
3.76
3.09
2.24
E5-07
PM q-axis Inductance
(mH/phase)
mH
14.60
11.40
10.64
8.16
6.80
4.88
4.75
3.03
E5-09
PM Back-EMF Vpeak
(mV/(rad/s))
mVs/rad
610.3
595.2
711.6
710.8
652.7
604.8
669.1
646.8
E5-24
PM Back-EMF L-L
Vrms (mV/rpm)
mV/min
-1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum Output
Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Maximum Output
Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Minimum Output
Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
C5-17
Motor Inertia
kgm
2
0.054
0.063
0.113
0.137
0.252
0.304
0.41
0.55
L3-24
Motor Accel Time @
Rated Torque
s
0.083
0.079
0.118
0.105
0.157
0.156
0.172
0.169
n5-02
Motor Inertia
Acceleration Time
s
0.083
0.079
0.118
0.105
0.157
0.156
0.172
0.169
n8-49
Heavy Load Id Current
%
-14.5
-16.1
-11.8
-10.5
-15.6
-17.4
-21.7
-17.3
*1
The default setting changes when the setting for
o2-04 [Drive Model Selection]
changes.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...