YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
399
OFF : During baseblock
■
1C: Motor 2 Selected
Setting Value
Function
Description
1C
Motor 2 Selected
The terminal activates when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
■
1D: During Regeneration
Setting Value
Function
Description
1D
During Regeneration
The terminal activates on when the motor is regenerating.
ON : Motor is regenerating.
OFF : Motor is operating or stopped.
■
1E: Executing Auto-Restart
Setting Value
Function
Description
1E
Executing Auto-Restart
The terminal activates when the Auto Restart function is trying to restart after a fault.
The terminal deactivates when the Auto Restart function automatically resets a fault. The terminal turns off when the
Auto Restart function detects the fault again since Auto Restart function cannot function any longer due to number of
attempts set with
L5-01 [Number of Auto Restart Attempts]
being reached.
Note:
Refer to "L5: Auto-Restart" for more information.
■
1F: Motor Overload Alarm (oL1)
Setting Value
Function
Description
1F
Motor Overload Alarm
(oL1)
The terminal activates when the electronic thermal protection value of the motor overload protective function is a minimum of 90%
of the detection level.
Note:
Refer to
“
L1-01: Motor Overload (oL1) Protection
”
for more information.
■
20: Drive Overheat Pre-Alarm (oH)
Setting Value
Function
Description
20
Drive Overheat Pre-Alarm
(oH)
The terminal activates when the drive heatsink temperature is at the level set with
L8-02 [Overheat Alarm Level]
.
Note:
Refer to
“
L8-02: Overheat Alarm Level
”
for more information.
■
21: Safe Torque OFF
Setting Value
Function
Description
21
Safe Torque OFF
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and when
terminals H1-HC and H2-HC are OFF (Open).
Note:
EDM = External Device Monitor
ON : Safety stop state
Terminals H1-HC and H2-HC are OFF (Open) (safety stop state).
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...