2.11 o: Keypad-Related Settings
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
525
Note:
The maintenance period changes for different operating environments.
■
o4-11: Fault Trace/History Init (U2/U3)
No.
(Hex.)
Name
Description
Default
(Range)
o4-11
(0510)
Fault Trace/History Init (U2/
U3)
Resets the records of Monitors
U2-xx [Fault Trace]
and
U3-xx [Fault History]
.
0
(0, 1)
Note:
When you initialize the drive with
A1-03 [Initialize Parameters]
, the drive will not reset the records for
U2-xx
and
U3-xx
.
0 : Disabled
Keeps the records of Monitors
U2-xx
and
U3-xx
.
1 : Enabled
Resets the records for Monitors
U2-xx
and
U3-xx
. After the reset, the drive automatically resets
o4-11
to
0
.
■
o4-12: kWh Monitor Initialization
No.
(Hex.)
Name
Description
Default
(Range)
o4-12
(0512)
kWh Monitor Initialization
Resets the monitor values for
U4-10 [kWh, Lower 4 Digits]
and
U4-11 [kWh, Upper 5 Digits]
.
0
(0, 1)
Note:
When you initialize the drive with
A1-03 [Initialize Parameters]
, the drive will not reset
U4-10
and
U4-11
.
0 : No Reset
Keeps the monitor values for
U4-10
and
U4-11
.
1 : Reset
Resets the values of
U4-10
and
U4-11
. After the reset, the drive automatically resets
o4-12
to
0
.
■
o4-13: RUN Command Counter @ Initialize
No.
(Hex.)
Name
Description
Default
(Range)
o4-13
(0528)
RUN Command Counter @
Initialize
Resets the monitor values for
U4-02 [Num of Run Commands]
,
U4-24 [Number of Runs (Low)]
, and
U4-25 [Number of Runs (High)]
.
0
(0, 1)
0 : No Reset
Keeps the monitor values for
U4-02
,
U4-24, and U4-25
.
1 : Reset
Resets the values of
U4-02
,
U4-24
, and
U4-25
. After the reset, the drive automatically resets
o4-13
to
0
.
■
o4-22: Time Format
No.
(Hex.)
Name
Description
Default
(Range)
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when using an LCD keypad.
1
(0 - 2)
Sets the display of the time shown in the upper-left of the LCD keypad screen.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...