TOEPYAIGA8002B GA800 Drive Programming
◆
n7: EZ Drive
The
n7 parameters
provide special adjustments for EZ Vector Control.
■
n7-01: Damping Gain for Low Frequency
No.
(Hex.)
Name
Description
Default
(Range)
n7-01
(3111)
Expert
Damping Gain for Low
Frequency
Sets the oscillation suppression gain for the low speed range.
1.0
(0.1 - 10.0)
Note:
•
If oscillation occurs in the low speed range, increase the acceleration time or increase the setting value in 0.5-unit increments.
•
To get starting torque with the setting for
C4-01 [Torque Compensation Gain]
, decrease the setting value in 0.3-unit increments.
■
n7-05: Response Gain for Load Changes
No.
(Hex.)
Name
Description
Default
(Range)
n7-05
(3115)
Expert
Response Gain for Load
Changes
Sets the response gain related to changes in the load.
100
(10 - 1000)
Note:
To make tracking related to load changes better, increase the setting value in 5-unit increments. If oscillation occurs during load changes,
decrease the setting value in 5-unit increments.
■
n7-07: Speed Calculation Gain1
No.
(Hex.)
Name
Description
Default
(Range)
n7-07
(3117)
Expert
Speed Calculation Gain1
Sets the speed calculation gain during usual operation. Usually it is not necessary to change this
setting.
15.0 Hz
(1.0 - 50.0 Hz)
■
n7-08: Speed Calculation Gain2
No.
(Hex.)
Name
Description
Default
(Range)
n7-08
(3118)
Expert
Speed Calculation Gain2
Sets the speed calculation gain during a speed search.
25.0 Hz
(1.0 - 50.0 Hz)
Note:
When you increase the setting value, you can do a speed search of a motor rotating at a high frequency. If the setting value is too high, the
calculated speed will oscillate and a restart will fail. Decrease the setting value in these conditions.
■
n7-10: Pull-in Current Switching Speed
No.
(Hex.)
Name
Description
Default
(Range)
n7-10
(311A)
Expert
Pull-in Current Switching
Speed
Parameter
n8-51 [Pull-in Current @ Acceleration]
, is in effect when the output frequency is ≤
n7-10
,
where the speed is set as a percentage of rated speed.
10.0%
(0.0 - 100.0%)
Note:
•
The value set in
n8-51 [Pull-in Current @ Acceleration
is enabled for speeds that are not higher than
n7-10
during deceleration. The value
set in
b8-01 [Energy Saving Control Selection]
is enabled for speeds higher than
n7-10
.
•
If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
•
When it is most important to save energy in the low speed range, decrease the setting value.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV