YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
461
When vibration occurs during operation of Single Drive KEB Ride-Thru 2, increase this parameter in 0.010-unit
increments.
Note:
The Single Drive KEB Ride-Thru 2 mode operates when
L2-29 = 1 [KEB Method Selection = Single Drive KEB Ride-Thru 2]
and
H1-xx =
7A or 7B [Terminal Sx Function Selection = KEB Ride-Thru 2 (N.C./N.O.)]
.
■
L3-35: Speed Agree Width for Auto Decel
No.
(Hex.)
Name
Description
Default
(Range)
L3-35
(0747)
Expert
Speed Agree Width for Auto
Decel
Sets the width for speed agreement when
L3-04 = 2 [Decel Stall Prevention Selection = Automatic
Decel Reduction]
. Usually it is not necessary to change this setting.
0.00 Hz
(0.00 - 1.00 Hz)
Set this parameter when hunting occurs while you use a frequency reference through an analog input.
■
L3-36: Current Suppression Gain@Accel
No.
(Hex.)
Name
Description
Default
(Range)
L3-36
(11D0)
Current Suppression
Gain@Accel
Sets the gain to suppress current and motor speed hunting during operation when
L3-01 = 3 [Stall
Prevention during Accel = Current Limit Method]
. Usually it is not necessary to change this setting.
Determined by A1-02
(0.0 - 100.0)
If there is vibration in the output current during acceleration, increase the setting value.
Note:
Set
L3-01 = 3 [Stall Prevention during Accel = Current Limit Method]
to enable this function.
■
L3-37: Current Limit P Gain @ Accel
No.
(Hex.)
Name
Description
Default
(Range)
L3-37
(11D1)
Expert
Current Limit P Gain @
Accel
Suppresses current hunting during acceleration. Usually it is not necessary to change this setting.
5 ms
(0 - 100 ms)
Note:
Set
L3-01 = 3 [Stall Prevention during Accel = Current Limit Method]
to enable this function.
■
L3-38: Current Limit I Time @ Accel
No.
(Hex.)
Name
Description
Default
(Range)
L3-38
(11D2)
Expert
Current Limit I Time @
Accel
Suppresses current hunting and overshooting that occurs when the drive stalls during acceleration.
Usually it is not necessary to change this setting.
10.0
(0.0 - 100.0)
Note:
Set
L3-01 = 3 [Stall Prevention during Accel = Current Limit Method]
to enable this function.
■
L3-39: Current Limit Filter Time @Accel
No.
(Hex.)
Name
Description
Default
(Range)
L3-39
(11D3)
Current Limit Filter Time
@Accel
Sets the time constant to adjust the acceleration rate when
L3-01 = 3 [Stall Prevention during Accel
= Current Limit Method]
. Usually it is not necessary to change this setting.
100.0 ms
(1.0 - 1000.0 ms)
Note:
Set
L3-01 = 3 [Stall Prevention during Accel = Current Limit Method]
to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...