d1-02: Reference 2
No.
(Hex.)
Name
Description
Default
(Range)
d1-02
(0281)
RUN
Reference 2
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM]
, the drive changes
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
To set
d1-02
to Multi-Step Speed 2, set
H3-02, H3-06, and H3-10 ≠ 2 [MFAI Function Select ≠ Auxiliary Frequency Reference 1]
. When
the status is the default setting, set
H3-06 = F [Terminal A3 Function Selection = Not Used]
.
■
d1-03: Reference 3
No.
(Hex.)
Name
Description
Default
(Range)
d1-03
(0282)
RUN
Reference 3
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM]
, the drive changes
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
To set
d1-03
to Multi-Step Speed 3, set
H3-02, H3-06, and H3-10 ≠ 3 [MFAI Function Select ≠ Auxiliary Frequency Reference 2]
.
■
d1-04: Reference 4
No.
(Hex.)
Name
Description
Default
(Range)
d1-04
(0283)
RUN
Reference 4
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM]
, the drive changes
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
This parameter sets the frequency reference of Multi-Step Speed 4.
■
d1-05: Reference 5
No.
(Hex.)
Name
Description
Default
(Range)
d1-05
(0284)
RUN
Reference 5
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change.
•
When
A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM]
, the drive changes
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
This parameter sets the frequency reference of Multi-Step Speed 5.
■
d1-06: Reference 6
No.
(Hex.)
Name
Description
Default
(Range)
d1-06
(0285)
RUN
Reference 6
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 590.00 Hz)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV