2.2 A: Initialization Parameters
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
177
•
High-precision torque control. A speed feedback signal from the motor is necessary for this control method. The
speed control range is 1:1500.
4 : Advanced Open Loop Vector
This is a control method for induction motors. Use this control method for applications in which high-precision speed
control is necessary.
This control method has high speed and torque response and high torque when operating at low speeds. The speed
control range is 1:200.
5 : PM Open Loop Vector
The drive controls an IPM motor or SPM motor in this control method. Use this control method for general variable-
speed control applications in which a high level of responsiveness or high-precision speed control are not necessary.
The speed control range is 1:20.
6 : PM Advanced Open Loop Vector
The drive can control an IPM motor in this control method. Use this control method for general variable-speed control
applications in which high-precision speed control and torque limit are necessary. The speed control range is 1:20.
The speed control range is 1:100 when
n8-57 = 1 [HFI Overlap Selection = Enabled]
.
7 : PM Closed Loop Vector
The drive controls a PM motor in this control method. Use this control method for constant torque applications in
which high-precision control with a PM motor is necessary. Also use this control method for general variable-speed
control applications in which high torque response and high-precision torque control are necessary. A speed feedback
signal from the motor is necessary for this control method. The speed control range is 1:1500.
8 : EZ Vector Control
The drive controls SynRM (Synchronous Reluctance Motors) in this control method. This control method uses an
easier procedure to operate motors with more efficiency. Use this control method for derating torque applications. For
example, fans and pumps.
■
A1-03: Initialize Parameters
No.
(Hex.)
Name
Description
Default
(Range)
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0
(0 - 3330)
Note:
•
After you initialize the drive, the drive automatically sets
A1-03 = 0
.
•
User Parameters can save the parameter values for your application and use these values as default values for drive initialization.
•
To use the 2 motor switchover function, first turn OFF the terminal to which
H1-xx = 16 [MFDI Function Selection = Motor 2 Selection]
is
set, then change the A1-03 setting. An incorrect procedure will trigger
oPE08 [Parameter Selection Error]
.
0 : No Initialization
1110 : User Initialization
Sets parameters to the values set by the user as user settings. Set
o2-03 = 1 [User Parameter Default Value = Set
defaults]
to save the user settings.
You can save the parameter settings that were adjusted for the test run as user-set default values to the drive. When
you make changes to the parameter values after you save the settings as User Parameter Settings, the drive will set the
parameters to the User Parameter Setting value when you initialize with
A1-03 = 1110
.
Follow this procedure to save User Parameter setting values, and to do a User Initialization.
1. Set parameters correctly for the application.
2. Set
o2-03 = 1 [User Parameter Default Value = Set defaults]
.
This saves parameter settings for a User Initialization.
The drive will then automatically set
o2-03 = 0
.
3. Set
A1-03 = 1110
to reset to the saved parameter settings.
When you initialize the drive, the drive sets the parameter values to the User Parameter setting values.
2220 : 2-Wire Initialization
Sets MFDI terminal S1 to Forward Run and terminal S2 to Reverse Run, and resets all parameters to default settings.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV