214
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Set Speed Search to
H1-xx
to do the function externally. You cannot set external Speed Search 1 and 2 at the same
time.
Table 2.23 Execute Speed Search via the Digital Input Terminals
H1-xx Setting
Name
Current Detection 2
Speed Estimation
61
Speed Search from Fmax
ON: Speed Search starts from
E1-04 [Maximum Output
Frequency]
.
External Speed Search commands 1 and 2 work the
same.
The drive estimates the motor speed, then starts Speed
Search from the estimated speed.
62
Speed Search from Fref
ON: Speed Search starts from the frequency reference
immediately before you input the Speed Search
command.
•
Do Speed Search with Each Auto Restart
Set
L5-01 [Number of Auto-Restart Attempts] = 1
or more. After there is an Auto Restart fault, the drive
automatically does Speed Search.
•
Do Speed Search after Momentary Power Loss
Set
L2-01 =1, 2 [Power Loss Ride Through Select = Enabled for L2-02 Time, Enabled while CPU Power Active]
.
•
Do Speed Search after You Clear the External Baseblock Command
After you clear the external baseblock command, enable the Run command, and when the output frequency is
higher than the minimum frequency, the drive does Speed Search.
■
b3-01: Speed Search at Start Selection
No.
(Hex.)
Name
Description
Default
(Range)
b3-01
(0191)
Speed Search at Start
Selection
Sets the Speed Search at Start function where the drive will perform Speed Search with each Run
command.
Determined by A1-02
(0, 1)
0 : Disabled
Enter a Run command to start to operate the drive at the minimum output frequency.
When the Run command is enabled and the
Speed Search from Fmax or Fref [H1-xx = 61, 62]
is input from a multi-
function input terminal, the drive will do Speed Search and start to operate the motor.
1 : Enabled
Enter the Run command to do Speed Search. The drive completes Speed Search then starts to operate the motor.
■
b3-02: SpeedSearch Deactivation Current
No.
(Hex.)
Name
Description
Default
(Range)
b3-02
(0192)
SpeedSearch Deactivation
Current
Sets the current level that stops Speed Search as a percentage of the drive rated output current.
Usually it is not necessary to change this setting.
Determined by A1-02
(0 - 200%)
If the drive cannot restart the motor, decrease this setting.
■
b3-03: Speed Search Deceleration Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-03
(0193)
Speed Search Deceleration
Time
Sets the deceleration time during Speed Search operation. Set the length of time to decelerate from
the maximum output frequency to the minimum output frequency.
2.0 s
(0.1 - 10.0 s)
This is the output frequency deceleration time used by Current Detection Speed Search and by the Current Injection
Method of Speed Estimation Speed Search.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this parameter takes effect only in Expert Mode.
•
If the drive detects
oL1 [Motor Overload]
during Current Detection Speed Search, decrease the value set in
b3-03
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...