TOEPYAIGA8002B GA800 Drive Programming
When the output current is unbalanced for longer than the time set in
L8-31
, the drive detects
LF2
.
Note:
•
Set
L8-29 = 1 [Output Unbalance Detection Sel = Enabled]
to enable
L8-31
.
•
If the drive incorrectly detects
LF2
, increase
L8-31
in 5-unit increments.
•
The keypad shows
L8-31
when
E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)]
in EZ Vector Control.
■
L8-35: Installation Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-35
(04EC)
Installation Method
Selection
Sets the type of drive installation.
Determined by the drive
(0 - 3)
Note:
•
Parameter
A1-03 [Initialize Parameters]
does not initialize this parameter.
•
This parameter is set to the correct value when the drive is shipped. Side-by-Side installation
–
Change the value only in these conditions:
–
When you install a UL Type 1 kit on an Open-chassis type (IP20) drive to convert the drive to an Enclosed wall-mounted type (UL Type
1).
The
overload
protection
detection
level
for
the
drive
is
automatically
adjusted
to
the
optimal
value
in
accordance
with
the
setting
value.
0
:
IP20/OpenChassis
Enc/Ex
Heatsink
Use
this
setting
to
install
an
open-chassis
type
(IP20)
drive
or
when
the
heatsink
(cooling
fin)
is
outside
of
the
enclosure
panel.
Make
sure
that
there
is
30
mm
(1.18
in)
minimum
of
space
between
drives
or
between
the
drive
and
side
of
the
enclosure
panel.
1
:
Side-by-Side
Mounting
Use
this
setting
to
install
more
than
one
drive
Side-by-Side.
Make
sure
that
there
is
2
mm
(0.08
in)
minimum
of
space
between
drives.
2
:
IP20/NEMA
Type
1/IP55
Use
this
setting
to
install
UL
Type
1
enclosed
wall-mounted
type
drives
or
IP55
drives.
3
:
Finless
Use
this
setting
to
install
a
finless
drive
(no
heatsink).
■
L8-38: Carrier Frequency Reduction
No.
(Hex.)
Name
Description
Default
(Range)
L8-38
(04EF)
Carrier Frequency Reduction
Sets the carrier frequency reduction function. The drive reduces the carrier frequency when the
output current is more than a specified level.
Determined by A1-02, C6-
01 and o2-04
(0 - 2)
If you decrease the carrier frequency, it increases the overload tolerance. The overload capacity increases temporarily
for
oL2 [Drive Overloaded]
and lets the drive operate through transient load peaks and not trip.
0 : Disabled
The drive will not decrease the carrier frequency at high current.
1 : Enabled below 6 Hz
The drive decreases the carrier frequency at speeds less than 6 Hz when the current is more than 100% of the drive
rated current.
When the current is less than 88% or the output frequency is more than 7 Hz, the drive goes back to the usual carrier
frequency.
2 : Enabled for All Speeds
The drive decreases the carrier frequency at these speeds:
•
Output current is a minimum of 100% of the drive rated current and the frequency reference is less than 6 Hz.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV