YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
219
■
b3-33: Speed Search during Uv Selection
No.
(Hex.)
Name
Description
Default
(Range)
b3-33
(0B3F)
Expert
Speed Search during Uv
Selection
Sets the function that starts Speed Search at start-up if the drive detects a
Uv [Undervoltage]
when it
receives a Run command.
1
(0, 1)
Set these three parameters as shown to enable
b3-33
:
•
L2-01 = 1, 2 [Power Loss Ride Through Select = Enabled for L2-02 Time, Enabled while CPU Power Active]
•
b3-01 = 1 [Speed Search at Start Selection = Enabled]
•
b1-03 = 1 [Stopping Method Selection = Coast to Stop]
0 : Disabled
1 : Enabled
■
b3-35: Low Back EMF Detection Level
No.
(Hex.)
Name
Description
Default
(Range)
b3-35
(0BC3)
Expert
Low Back EMF Detection
Level
Sets the Low Back EMF Detection Level. Usually it is not necessary to change this setting.
10%
(5 - 50%)
■
b3-36: High Back EMF Detection Level
No.
(Hex.)
Name
Description
Default
(Range)
b3-36
(0BC4)
Expert
High Back EMF Detection
Level
Sets the voltage level for Speed Search restart. Usually it is not necessary to change this setting.
0.970
(0.500 - 1.000)
The drives wait for Speed Search to prevent failure when the induced voltage for the motor during coasting to a stop
is larger than the voltage the drive can output. The drive will not restart the motor (Speed Search) if induced voltage ≥
supply voltage ×
b3-36
after a Run command is entered. The drive will restart the motor when induced voltage <
supply voltage ×
b3-36
. For example, if the setting value is 0.83 and the voltage does not decrease to the induced
voltage at approximately 183 V when the power supply voltage is 220 V, the drive will not restart.
■
b3-54: Search Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-54
(3123)
Search Time
Sets the length of time that the drive will run Speed Search.
400 ms
(10 - 2000 ms)
If you set this parameter too low, Speed Search will not operate correctly.
If the drive detects
oC [Overcurrent]
immediately after Speed Search Starts:
•
Increase the value of
L2-03 [Minimum Baseblock Time]
and decrease the motor speed you use to start Speed
Search.
•
Increases the setting value of
b3-08 [Speed Estimation ACR P Gain]
.
•
Increase the value of
b3-54
.
If the drive detects
oC
or
ov [DC Bus Overvoltage]
during Speed Search, increase the value of
b3-08
.
■
b3-55: Current Increment Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-55
(3124)
Expert
Current Increment Time
Sets the length of time that the drive will increase the current from zero current to the setting value of
b3-06 [Speed Estimation Current Level 1]
.
10 ms
(10 - 2000 ms)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...