Output current is a minimum of 109% of the drive rated current, the drive is in Normal Duty mode, and the
frequency reference is 7 Hz or more.
•
Output current is a minimum of 112% of the drive rated current, the drive is in Heavy Duty mode, and the
frequency reference is 7 Hz or more.
When the drive switches the carrier frequency to the set value, it uses the delay time set in
L8-40 [CarrierFreqReduct
Off DelayTime]
and a hysteresis of 12%.
■
L8-40: Carrier Freq Reduction Off-Delay
No.
(Hex.)
Name
Description
Default
(Range)
L8-40
(04F1)
Carrier Freq Reduction Off-
Delay
Sets the length of time until the automatically reduced carrier frequency returns to the condition
before the reduction.
Determined by A1-02
(0.00 - 2.00 s)
Set
L8-40 ≠ 0.00
to enable the carrier frequency reduction function during start-up. When operation starts, the drive
automatically decreases the carrier frequency. When the time set in
L8-40
is expired, the carrier frequency returns to
the value set in
C6-02 [Carrier Frequency Selection]
.
When
L8-38 = 1, 2 [Carrier Frequency Reduction = Enabled]
, the drive applies
L8-40
as the time for the carrier
frequency to return to its configured value after it is decreased.
■
L8-41: High Current Alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-41
(04F2)
High Current Alarm
Selection
Sets the function to cause an
HCA [Current Alarm]
when the output current is more than 150% of the
drive rated current.
0
(0, 1)
0 : Disabled
The drive will not detect
HCA [Current Alarm]
.
1 : Enabled
If the output current is more than 150% of the drive rated current, the drive will detect
HCA
.
The MFDO terminal set for an alarm
[H2-01 to H2-03 = 10]
activates.
■
L8-51: STPo I Detection Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-51
(0471)
Expert
STPo I Detection Level
Sets the
STPo [Motor Step-Out Detected]
detection level as a percentage of the motor rated current.
0.0%
(0.0 - 300.0%)
Note:
The detection level is automatically calculated when
L8-51 = 0
.
■
L8-52: STPo Integration Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-52
(0472)
Expert
STPo Integration Level
Sets the detection level for
STPo [Motor Step-Out Detected]
related to the ACR integral value.
1.0
(0.1 - 2.0)
■
L8-53: STPo Integration Time
No.
(Hex.)
Name
Description
Default
(Range)
L8-53
(0473)
Expert
STPo Integration Time
Sets the length of time until the drive detects
STPo
after it is more than the value of
L8-51 [STPo I
Detection Level]
.
1.0 s
(1.0 - 10.0 s)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV