Figure 2.78 3-Wire Sequence Time Chart
Note:
•
To input the Run command, activate the terminal for 1 ms minimum.
•
The default setting for
b1-17 [Run Command at Power Up]
is
0 [Disregard existing RUN command]
. If you enable the Run command when
the drive is energized, the protective function activates and the
flashes quickly. When the application allows Run, set
b1-17 = 1
[Accept Existing RUN Command]
.
■
1: LOCAL/REMOTE Selection
Setting Value
Function
Description
1
LOCAL/REMOTE Selection
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
Note:
•
When the MFDI terminal sets the LOCAL/REMOTE selection,
on the keypad is disabled.
•
When LOCAL Mode is selected, the green light for
comes on.
•
When the Run command is ON, you cannot switch between LOCAL Mode and REMOTE Mode.
ON : LOCAL
The keypad is the Frequency reference source and Run command source.
OFF : REMOTE
The frequency reference and Run command settings are set in
b1-01
,
b1-02 [Frequency Reference Selection 1/2]
or
b1-15
,
b1-16 [Run Command Selection 1/2]
.
■
2: External Reference 1/2 Selection
Setting Value
Function
Description
2
External Reference 1/2
Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
Note:
When the drive is receiving a Run command, you cannot switch between reference sources.
ON :
b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF :
b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
■
3: Multi-Step Speed Reference 1
Setting Value
Function
Description
3
Multi-Step Speed Reference
1
Uses speed references
d1-01 to d1-16
to set a multi-step speed reference.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV